6.2.4 Grounding
Earth connection is essential BEFORE connecting supply.
1. Switch off all the breakers in the distribution panel.
2. Remove the roof by loosening the two screws at the front, which hold the top in position. Pull the top
forward and lift it up.
3. Connect the grounding cable between the grounding connector in the positive DC busbar of the
cabinet and the main grounding point at the back of the cabinet.
4. Check that the cables are secured tightly.
6.2.5 Cable sizes / location of external connections
Mains:
Max. 16 mm
2
(4AWG)
Alarms:
Max. 1,5 mm
2
(14AWG)
Load:
Max. 16 mm
2
/ 35 mm
2
(4AWG / 1AWG)
Battery:
Max. 35 mm
2
(1AWG) (50mm
2
(0AWG) w / cable lug)
Alarm connections are located at the top right side of the system.
6.2.5.1
Cable entry box
The cable entry box delivered with the system (or additional cable entry kit option) should be mounted
before connecting mains and load. Remove or lift the cabinet top before installing the cable entry box. Once
a cable entry side is selected (rear, left or right) the panel in the selected position is replaced with the panel
in
. Default cable entry side is to the right, so no panel is mounted in this position. Do not remove
the panel during cable installation. Follow steps 1 through 5 below to complete installation of the cable entry
box.
Figure 6-3 Cable entry casing.(Shown without nipples)
1.
Select cable entry side and remove the cover where mounted. If rear or left cable entry is wanted,
the cover mounted here can be moved to the right side.
2.
Fasten the cable entry casing to the cabinet with three M4 screws.
Mains cable entry
Load/Battery/Signal
cable entries
Battery tube entry
Summary of Contents for PODS 16.48-16000 1940 HEX
Page 4: ...1 2 PODS 16 48 16000 1940 HEX Document number titlepage fm Revision B...
Page 10: ...2 6 PODS 16 48 16000 1940 HEX Document number 039158TOC fm Revision B...
Page 23: ...Safety 5 1 Document number 028580 fm Revision A Safety 5 Safety...
Page 40: ...6 14 PODS 16 48 16000 1940 HEX Document number 039160 fm Revision A Installation guide...
Page 41: ...Commissioning 7 1 Document number 036285 fm Revision A Commissioning 7 Commissioning...
Page 92: ...A 10 PODS 16 48 16000 1940 HEX Document number Appendix A fm Revision B Drawings...
Page 94: ...B 2 PODS 16 48 16000 1940 HEX Document number 039418 fm Revision B Configuration c 000313...
Page 95: ...Configuration c 000313 B 3 Document number 039418 fm Revision B Configuration c 000313...
Page 96: ...B 4 PODS 16 48 16000 1940 HEX Document number 039418 fm Revision B Configuration c 000313...