background image

1.

3.

2.

4.

6.

5.

7.

IMPORT

ANT SAFE

TY INSTR

UC

TION

QUICK INST

ALL

ATION GUIDE

SELECT INSTALLATION LOCATION

SWITCHBOX WIRING DETAIL

WALL MOUNTING

DC ARRAY CONNECTIONS - INDEPENDENT MODE

AC GRID CONNECTIONS

DC ARRAY CONNECTIONS - PARALLEL MODE

SIGNAL WIRING CONNECTIONS

QUICK INST

ALL

ATION GUIDE

AUR

OR

A P

VI-5000/6000-

TL

AUR

OR

A P

VI-5000/6000-

TL

AUR

OR

A P

VI-5000/6000-

TL

QUICK INST

ALL

ATION GUIDE

QUICK INST

ALL

ATION GUIDE

BCM.00163.0_AA

Quick Installation Guide

AURORA PVI-5000/6000-TL

This Quick Installation Guide is offered in addition to the full Technical 

Manual which can be found on the CD accompanying this guide and the 

Power-One Renewable Energy website at: http://www.power-one.com.
The installation is to be done according to the applicable local code 

regulations (National Electric Code (NEC), Canadian Electric Code (CEC), 

and/or other local codes and regulations).
This Quick Installation Guide applies to the following AURORA® UNO 

Inverter transformerless models:

PVI-5000-OUTD-US, PVI-5000-OUTD-US-A

PVI-6000-OUTD-US, PVI-6000-OUTD-US-A

All model dimensions are 41.4”H x 12.8”W x 8.6”D and weigh 59.5 lbs (27 

kg).The -A model includes an Integrated PV AFCI Type 1 device for arc fault 

detection (AFD section 12) mounted on the rail in the wiring box (Figure 2). 

Wiring connections are the same for both models unless specified.

SAVE THESE INSTRUCTIONS - KEEP IN A SAFE PLACE!

This is a list of special safety symbols used in this guide. The symbol usage is as follows:

CAUTION:

 

Indicates directions which must be understood and followed in order to avoid 

potential safety hazards, including equipment damage or personal injury.

DANGEROUS VOLTAGE:

 

The product works with high voltages. During inverter operation, 

parts will be energized at voltage levels.

HOT TEMPERATURE:

 

Some surfaces may become hot. Do not touch the product while it is 

in operation.
UL 1741 Standard for Safety for Inverters, Converters, Controllers and nterconnection System 

Equipment for use with Distributed Energy Resources. CSA-C22.2 No. 107.1-01 - General Use 

Power Supplies.

ELECTRICAL CONNECTION WARNINGS

 - The PV source conductors must be Listed PV wire per NEC 

690.35. PV output conductors shall consist of sheathed (jacketed) multi-conductor cables or installed 

in an approved raceway and must be isolated from the enclosure and system grounding, as required by 

NEC 690.35 and is the responsibility of the installer.
An external DC switch must be used if not integrated in the inverter. All models listed above have an 

integrated DC switch.
The inverter shall be connected only to a dedicated branch circuit provided with the maximum branch 

OCPD listed in the Technical data sheet, section 

14

. To reduce the risk of fire, connect only to a circuit 

provided with 25A, 30A, 35A for PVI-5000-OUTD-US(-A) or 30A, 35A, 40A for PVI-6000-OUTD-US(-A) 

maximum branch circuit overcurrent protection in accordance with the NEC (ANSI/NFPA 70).
The installer and/or operator must protect the installation from access by the public and/or highlight 

with signs or notices the hazards of the equipment.

Select a well-ventilated location sheltered from direct sun radiation or any other heat source (other 

inverters). Choose a location that allows unobstructed airflow around the inverter. Maintain minimum 

clearance distances shown.

                    

For multiple inverter installations, position the inverters side-by-side or in a staggered arrangement so 

heat dissipation does not affect other inverters; maintain minimum clearances shown.

Package contents include:

1

 AURORA Inverter

1

 Mounting bracket

1

 Hardware bag containing:

     

2

 - Terminal connectors

     

4

 - 6.3 x 70mm screws

     

4

 - S x 10 wall plugs

     

1

 - Red cable AWG #10

     

1

 - Black cable AWG # 10

     

1

 - 6 x 10mm machine screw

     

1

 - 6mm flat washer

     

1

 - Torx 20 wrench

1

 Quick Installation Guide

1

 CD with Software, Warranty, and full    

    Technical Manual

The inverter can be configured with two independent maximum power point tracking (MPPT) channels 

(Figure 3) or as a single channel with one MPPT by paralleling the two channels (Figure 4 and Figure 5). 

Switch S1 (Figure 6), is used to select parallel (

PAR

) or independent (

IND

) input mode.

To access the switchbox wiring and Switch S1, loosen the four captive screws on the front covers using 

the Torx wrench provided.

Before removing front covers, DC switch must be in the OFF position.

Using DC knockouts (Figure 1), connect raceway from the PV array conduits to the DC array. Pull array 

wiring through and connect to String 1 and String 2 as shown in Figure 3.

 TO STRING 1

 TO STRING 2

 TO STRING 4

(OPTIONAL)

 TO STRING 3

(OPTIONAL)

Input Mode Switch S1 in IND 

(down) default position

Switch S1, located on the 

inverter connection board, 

Figure 6, is set in IND 

position (DOWN) by default.

Figure 1: Switch and wiring box external/ internal view

Connect array to String 1 and String 2 input positions shown, running separate wires for POS and NEG 

for each array. Up to four strings can be connected in the INDEPENDENT mode.
To connect four strings, String 3 and String 4 are connected in addition to 1 and 2, running separate 

wires for POS and NEG for each array.

The maximum allowable input short circuit current limit of the PV array for each MPPT 

input channel is 22Adc.

Array equipment grounding must be installed per the requirements of the NEC and is 

the responsibility of the installer. The transformerless design requires that the PV array 

to be floating with respect to ground per NEC 690.35.

Power-One DOES NOT provide AC output overcurrent protection; it is the 

responsibility of the end user to provide protection for the AC output circuit.

The AC grid wiring is connected through the inverter switchbox. Run an 

approved raceway between inverter and external AC disconnect switch. 

Make conduit entry through openings 

B

 or 

E

 shown in Figure 1. Connect 

AC wiring to switch box terminal block J and the main AC ground cable to 

switchbox terminal block 

K

.

Table 1, (which is also found on a label in the switchbox), shows AC wiring 

connections according to the AC grid type; connect wiring to the numbered 

terminals based on selected grid type.

Size conductors per NEC Article 310; Use 90°C copper wire only.

Terminal block accommodates wire size range of 14-4 AWG.

Table 1: Grid standard

The default 240V-SPLIT-PHASE connection requires the grid Neutral to be connected 

for proper operation.

Before connecting the inverter to the grid, the grid type must be selected if it differs 

from the default 240V-SPLIT-PHASE setting. See Section 9 for instructions to change 

the default.

* IMPORTANT: If several AURORA inverters are installed to a three-phase AC GRID, 

always distribute the inverters between the phases in order to reduce power 

imbalance between the phases. Always refer to the local standards.

PARALLEL TWO INPUTS WHEN:

The current from PV array exceeds 22 Adc or the array power exceeds limit for 

single channel (section 

14

). Refer to section 

4

 to access the switchbox wiring 

and and connect raceway from the PV array conduits to the DC array. Place 

switch S1 in the PAR position (UP) to configure inverter in parallel mode.

For -S versions only, in the switchbox

, parallel the two MPPT inputs of 

terminal [–IN1 and –IN2] and [+IN1 and +IN2],using the two #10 AWG jumper 

wires (provided with inverter), 1 black and 1 red, connecting the input as shown 

in Figure 4.

For -A versions only, in the inverter box

, parallel the two MPPT inputs of 

terminal [–IN1 and –IN2] and [+IN1 and +IN2] , using the two #10 AWG jumper 

wires (provided), 1 black and 1 red, connecting the input as shown in Figure 5.

Input Mode Switch 

S1 in PAR (UP)

position

 TO STRING 1  TO STRING 2

Paralleling jumpers 

required for

PARALLEL input 

mode operation

-S version only

Paralleling jumpers required for

PARALLEL input mode operation

-A version only

Figure 4: Parallel connection of DC array  

in the switchbox -S version

Figure 5: Parallel connection of DC array 

in the inverter box -A version

S

R

Q

T

P

Label Inverter Connection Board Details

P

Input Mode Selector Switch S1

Q

External alarm Out Terminals

R

RS-485 Terminal Block*

S

RS-485 RJ45 Connector**

T

RS-485 Line Termination Resistor Switch S2

* REM-Remote control not available for -A model; 

teR not accessible with AFD
** DO NOT CONNECT pin #4 when cabling units 

with AFD installed.

Figure 6: Inverter connection board

Wiring for the RS-485 communication system and hardwired control options are routed through the 

switchbox (openings 

D

 of Figure 1) and into the main inverter chassis for termination. Alarm and 

monitoring connections are shown as items 

Q

 and 

R

 in Figure 6. If the terminal blocks are used, the 

signal RTN, +T/R and –T/R have to be cabled.

RS-485 cable must be NRTL certified and provided 

with additional protection by means of a non-

metallic tubing.

 Use Belden #3106A (or eq.) cable for 

the RS-485 signals (RTN, ±T/R); ensure the ±T/R pair is 

connected through the cable twisted pair. Strip 1/4” 

insulation from all wires and connect to terminal block 

as indicated in Figure 7.

Figure 7: Signal wiring terminal block

Systems with multiple inverters require the RS-485 cable to be daisy chained inverter-to-inverter and 

there will be up to two RS-485 cables entering the inverter.

If a daisy chain connection is required for AFD installed inverters (-A models) use standard 

multiconductor RS-485 cable and connect the three RS-485 leads (-RTN, +T/R, -T/R) USING ONLY 

THE TERMINAL BLOCK. Do not use RJ45 connectors with AFD installations.

Locate Switch S2 on the inverter 

board (Figure 6, label 

T

). Confirm 

the switch is up in the OFF position 

for every inverter in the chain 

except for the last inverter, which 

must be turned ON.

Last inverter in Daisy Chain needs to have the switch S2 pushed 

down into the ON position (Termination resistor active).

The default position of the S2 switch in the OFF position.

Inverter default address is 2.

If multiple inverters are connected in a daisy chain, each unit must be assigned a different RS-485 

address. Refer to section 

9

 for instructions to assign addresses using the display menu.

The sum total length for all the RS-485 lines in the system must be less than 1000m (~1100 yards). 

Communications cabling must not be combined into the AC or DC power conduits; run these in a 

separate conduit.

Using the mounting bracket as a template, locate and 

mark the desired mounting location.
Mount bracket to wall using four screws (provided) 

through holes 

B

. Two additional screws can be used in 

position 

A

 if necessary.

Orient the bracket so the hooks 

C

 face out and up.

Hang the inverter on the bracket by lifting up 

and over the mounting plate, engaging the 

brackets 

C-D

 and 

E-F

 on the back.

Secure chassis bottom using machine screw 

and washer (provided) through center bottom 

hole 

H

, engaging threaded insert in the bracket 

G

. Add additional screws as necessary through 

bottom flange securing to mounting surface.

All -S and -A models have an integrated DC disconnect switch rated 600V/25A per contact. Maximum 

array DC voltage input to each MPPT circuit is 600 Vdc under any condition.

The switch disconnects the DC current from the PV panels in the “OFF” position. The 

inverter will stop producing power, but DOES NOT disconnect the AC from the grid.

Label

Description 

DC conduit entry plastic 

threaded plugs trade size 3/4”, 1” 

B

AC conduit entry plastic 

threaded plugs trade size 3/4”, 1”

C

DC Disconnect Switch

D

Signal cable opening with 

plastic threaded plug, 1/2” trade 

size

E

AC power cable opening with 

plastic threaded plug; trade size 1”

F

DC power cable opening with 

plastic threaded plug; trade size 

3/4”, 1”

H

Cover screws (4)

J

AC grid output terminals, NOTE 1

K

AC main ground, NOTE 2

L

Array PE ground, NOTE 1

M

AFD board (

-A only

)

Figure 1: Switch and wiring box external/ internal view

MPPT1 and MPPT2 DC array input, Note 1

M

NOTE 1:

 DC array wiring and ground 

terminals are spring pressure type and 

accommodate a wire size range of 16-6 

AWG. AC output terminals are spring 

pressure type and accommodate a wire 

size range of 14-4 AWG.

NOTE 2:

 AC ground terminals are spring 

pressure type and accept 16-4 AWG wire.

Figure 2: Switch and wiring box with AFD mounted 

on din rail -A model only (label M) AFD/ internal view

Reviews: