![Power Electronics SD750K Hardware And Installation Manual Download Page 54](http://html1.mh-extra.com/html/power-electronics/sd750k/sd750k_hardware-and-installation-manual_1586660054.webp)
SD750K
POWER ELECTRONICS
52
POWER CONNECTION
EN
EMC installation requirements
Introduction
The EMC European Directive defines electromagnetic compatibility as the capability of an apparatus,
an industrial plant, or a system to work satisfactorily in the electromagnetic environment without at the
same time causing electromagnetic disturbances in the apparatus, industrial plant or systems present
in the same environment.
The Electromagnetic Compatibility (EMC) depends on two main characteristics of the equipment:
Electromagnetic Interference (EMI) and Electromagnetic Susceptibility (EMS). The EMC standards
aims to ensure that all the electrical equipment that could operate simultaneously in the same
environment are compatible. This means that the interference immunity of all the devices is greater
than the interference emission of all the devices within the same environment.
The EMC requirements for Power Drive System (PDS) are defined in IEC/EN 61800-3 standard that is
included in the Declaration of conformity CE enclosed. In the European Union, EN61800-3 standard
takes priority over all generic standards. The PDS in the context of this standard comprises the drive
converter, the motor cables and the motor. Therefore, the installer as the ultimate responsible must
follow the installation instructions given within this manual.
Depending on the location of the drive, the standards define four categories distributed in two
environments.
•
First Environment:
Domestic installations. It also includes premises directly connected to a
low-voltage power supply network without an intermediate transformer which supplies
buildings used for domestic purposes such as shopping malls, cinemas, hospitals…
•
Second environment
: Industrial installations. Second Environment includes all plants other
than those directly connected to the public low-voltage network which supplies buildings used
for domestic purposes, e.g. factories and those other premises supplied by their own
dedicated transformer.
Summary of Contents for SD750K
Page 1: ...SD750K HARDWARE AND INSTALLATION MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE...
Page 2: ......
Page 59: ...POWER ELECTRONICS SD750K POWER CONNECTION 57 Connections for frame 2...
Page 60: ...SD750K POWER ELECTRONICS 58 POWER CONNECTION EN Connections for frame 3...
Page 61: ...POWER ELECTRONICS SD750K POWER CONNECTION 59 Connections for frame 4...
Page 83: ...POWER ELECTRONICS SD750K INDUCTANCES 81 Dimensions of inductances P246B Inductance...
Page 84: ...SD750K POWER ELECTRONICS 82 INDUCTANCES EN P256A Inductance...
Page 85: ...POWER ELECTRONICS SD750K INDUCTANCES 83 P233A Inductance...
Page 86: ...SD750K POWER ELECTRONICS 84 INDUCTANCES EN P297A Inductance...
Page 87: ...POWER ELECTRONICS SD750K INDUCTANCES 85 P298A Inductance...
Page 88: ...SD750K POWER ELECTRONICS 86 INDUCTANCES EN P316A Inductance...
Page 89: ...POWER ELECTRONICS SD750K INDUCTANCES 87 P317A Inductance...
Page 90: ...SD750K POWER ELECTRONICS 88 INDUCTANCES EN P318A Inductance...
Page 91: ...POWER ELECTRONICS SD750K INDUCTANCES 89 P319A Inductance...
Page 99: ......