POWER ELECTRONICS
SD300
CONTROL CONNECTION
79
Pulse Output Signals Connection in IP66 Drives
In IP66 drives, the pulse output signal is shared with the Q1 terminal. This
terminal must be set as TO in the parameter G6.33 and the next
connections must be performed to use it as a train pulse output:
•
Connect a 1/4W, 560Ω resistor between VR and Q1
terminals.
•
Connect EG and CM terminals.
Recommended Cable Section
The recommended wire characteristics are summarized in the table below.
The wire length of the safety input should not exceed 30m.
Terminal Type
Recommended wire size [mm
2
]
(AWG)
Screw
Torque
[N.m]
No crimp-style
terminal
Crimp-style
terminal
P1
–
P7, CM
0.75 (18)
0.5 (20)
M2 (1/32“)
0.22 ~ 0.25
VR
V1
I2
AO
Q1
EG
24
TI
TO
SA, SB, SC
S+, S-, SG
A1, B1, C1
1.0 (17)
1.5 (15)
M2.6 (3/32“)
0.4
A2, C2
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......