POWER ELECTRONICS
SD300
DESCRIPTION OF PROGRAMMING PARAMETERS
149
Screen Description
Default
value
Range
Function
Set on
RUN
Cn.53
Torque limit
reference
LOCAL 0 to 12
Select the source to introduce the torque
limit reference.
OPT. DESCR. FUNCTION
0
LOCAL
Reference will be given
by keypad and will be
set in (dr.2)
–
Local
Torque.
2
V1
Reference
will
be
introduced through the
voltage analog input 1.
4
V2
Reference
will
be
introduced through the
voltage analog input 2.
5
I2
Reference
will
be
introduced through the
current analog input 2.
6
MODBUS
The reference will be
introduced
through
Modbus.
8
COMMS
The reference will be
introduced through the
communications.
9
PLC
The common area can
be linked with user
sequence output and
can be used as
command.
12
PULSE
Reference
will
be
introduced through the
Pulse input.
NO
Cn.54
[19]
Forward
positive torque
limit
180.0%
0.0 to
200.0%
The user can set the forward motoring
operation torque limit whenever the torque
limit reference has been set as LOCAL.
YES
[19] Displayed when dr.9 is set to 4 (Sless-1). This will change the initial value of Ad.74,
Torque limit, to 150%.
Summary of Contents for SD 300 Series
Page 1: ...SD300 GETTING STARTED MANUAL LOW VOLTAGE VARIABLE SPEED DRIVE ...
Page 2: ......
Page 3: ...Variable Speed Drive Getting Started Manual Edition February 2019 SD30IM01GI Rev G ...
Page 159: ...POWER ELECTRONICS SD300 DESCRIPTION OF PROGRAMMING PARAMETERS 157 Power off delay ...
Page 174: ...SD300 POWER ELECTRONICS 172 DESCRIPTION OF PROGRAMMING PARAMETERS TI configuration ...
Page 352: ......
Page 353: ......