Recommended Renewal Parts and Replacement Procedures
PowlVac
®
STD Vacuum Circuit Breaker
IB-60201
Table F Control Devices
Control
Voltage
Primary Shunt Trip Coil
Assembly (2)
Secondary
Shunt Trip
Coil Assembly
(3)
Undervoltage
Device
Assembly (4)
Charging
Motor
Assembly
Anti-Pump
Relay (5)
Closing Coil
Assembly
3-Cycle
5-Cycle
24VDC
50027G05P
50041G08P
50042G06P
50028G08P
n/a
n/a
n/a
48VDC
50027G01P
50041G01P
50042G01P
50028G07P
50960G06P
RR2BA-US-
DC48V
50026G01P
125VDC
50027G02P
50041G02P
50042G03P
50028G10P
50960G04P
RR2BA-US-
DC110V
50026G03P
250VDC
50027G03P
50041G03P
50042G04P
50028G06P
50960G05P
RR2BA-US-
DC110V
50026G04P
120VAC
50027G01P
50041G05P
50042G01P
n/a
50960G04P
RR2BA-US-
AC120V
50026G01P
240VAC
50027G06P
50041G06P
50042G02P
n/a
50960G05P
RR2BA-US-
AC240V
50026G02P
Capacitor Trip
(6)
50027G04P
50041G04P
50042G05P
n/a
n/a
n/a
n/a
Notes:
1) One required per circuit breaker if the circuit breaker was originally equipped with this item. All
circuit breakers have a closing coil, primary shunt trip coil, charging motor, and an anti-pump
relay assembly. Secondary shunt trip coils and undervoltage device assemblies are optional
(see notes 2-7).
2) Primary shunt trip coil is available as a 3 cycle and 5 cycle control device. Trip coil assemblies
must only be replaced with the same type as originally supplied.
3) Secondary shunt trip coil cannot be furnished with an undervoltage device assembly.
4) Where furnished, cannot be present with secondary shunt trip coil assembly.
5) For 250VDC applications, a dropping resistor 50747G02P is required in series with the
anti-pump relay assembly.
6) For use with capacitor trip units with 240VAC input. Consult factory for other circuit breaker
ratings.
7) All control devices are available with push-on terminals. Consult factory for control devices
with screw terminals.