Powered by Safety
®
21
Installation
01.4IB.48040C
e. c
Onnect
n
etwOrk
And
p
Ower
w
iring
1) Power Requirements
The G3 Conversion Module requires a
12-24VDC voltage source to operate. Any
industrial DC power source that provides
power within the range specified can be
used. When selecting a DC power supply,
ensure that it is capable of providing
enough power for all of the units that it will
be supplying. Each unit requires 3 Watts
of power under maximum load conditions,
and considerably less during normal
operations. Ensure to add capacity if the
power supply will be used for supplying
peripherals such as MODBUS gateways.
2) Remove Terminal Connector
Begin by removing the Terminal Connector
from G3 Conversion Module. This is easily
done by hand or by prying a screwdriver
between it and its mating connector. Make
sure to loosen connector flange securing
screws.
Figure 24 Terminal Connectors of G3
Conversion Module
Ensure the power is turned OFF to prevent
damage to the equipment prior to connecting
the power of circuitry.
!
CAUTION
3) Connect DC Power Wiring
With the Terminal Connector labeled “6-10”
removed, connect the wires as indicated
. Secure the wires into place by
using a standard slot screwdriver. For short
local connection (<3 m/10 ft) inside the
low voltage compartment use unshielded
duplex wire such as Belden #8442. For
longer runs use twisted shielded cable such
as Belden #3105 or similar.
Table D Terminals 6-10
Terminal
Number
Name
Function
Wire
Gauge
Wire
Type
6
V-
Input Voltage
Negative
22
Unshielded
(<3 m/
10 ft)
Shielded
(<3 m/
10 ft)
7
V+
Input Voltage
Positive
8
PE
Chassis
Grounding
9
COM
Relay:
Common
Terminal
10
NO
Relay:
Normally
Open
Terminal
Summary of Contents for BriteSpot BSG3
Page 1: ...Instruction Bulletin 01 4IB 48040C BriteSpot BSG3 Powered by Safety ...
Page 4: ...Powered by Safety BriteSpot BSG3 01 4IB 48040C This page is intentionally left blank ...
Page 10: ...Powered by Safety BriteSpot BSG3 01 4IB 48040C This page is intentionally left blank ...
Page 37: ...Powered by Safety 27 Usage 01 4IB 48040C Figure 34 LCD Menu and Navigation ...