2. Set the following parameters on the boiler:
Tab.43 Boiler settings
Parameter number
Parameter
Setting
5710
Temps / mode CH1
Off
6020
Function extension module 1
Multifunctional
6046
Function input H2 module 1
Consumer request VK1 10V
6049
Voltage value 1 H2 module 1
0,5
6050
Funct value 1 H2 module 1
250
6051
Voltage value 2 H2 module 1
6052
Funct value 2 H2 module 1
(1) Default setting
(2) This parameter setting is an example. The value 800 means that, at 10 V, the set point will be 80°C.
For more information, see
Connection diagram: controlling a boiler in 0-10 V, page 35
Electrical connection: controlling a boiler in 0-10 V, page 52
Modifying the installer parameters, page 68
List of installer parameters, page 73
7.5.4
Configuring a master boiler and the slave boilers in a
cascade
1. Access the installer parameters of the master boiler.
2. Set the following parameters on the master boiler:
Tab.44 Configuration of the master boiler in a cascade
Parameter number
Parameter
Setting
Description
5977
Function input H5
None
Deactivation of the thermostat
on terminal block M1 (1–2)
6030
Relay output QX21 module 1
heating pump CH1 Q2
Check on the pump on circuit
1
6040
Sensor input BX21 module 1
Common flow sensor B10
Check on the cascade dis
charge temperature
6041
Sensor input BX22 module 1
Cascade return sensor B70
Check on the cascade return
temperature
6200
Save sensors
Yes
Saving any modifications
made.
The setting will revert automat
ically to No immediately after
the adjustment.
6630
Cascade master
Always
Identification master boiler
6640
Clock mode
Autonomously
Cascade master boiler clock
setting
3. Access the installer parameters of the slave boiler(s):
4. Set the following parameters on the slave boiler(s).
Tab.45 Cascade configuration of the slave boilers
Parameter number
Parameter
Setting
Description
5710
Temps / mode CH1
Off
Deactivation of the thermostat
on terminal block M1 (1–2)
6600
Device address
2...3...4...
Cascade activation
6640
Clock mode
Slave with remote setting
Setting the slave boiler clock
with a master boiler
7 Commissioning
7609493 - v08 - 24072018
67