8.1 INSTALLING THE CONTROL PANEL ON THE WALL
For the boiler to work with the Control Panel mounted on the wall, purchase accessory
B
supplied with the base
B1
and position it
on the boiler as shown in the figure. Also see the mounting and operation instructions supplied with the kit
B
. Proceed as follows:
•
Switch off the boiler.
•
Pass the three wires from the boiler terminal block
M2
through the hole in the base
B1
to apply to the wall.
•
Connect wires
1-2-3
of the boiler terminal block
M2
to terminals
(1)-(2)-(3)
of the base terminal block
B1
respectively.
•
Fix the base
B1
to the wall using the expansion grips and screws supplied with the accessory.
•
Apply the Control Panel
A
to the base fixed to the wall, taking care not to apply excessive force.
•
Place accessory
B
on the front boiler panel.
•
Power the boiler making sure that the Control Panel lights up.
The wire (1) from the boiler terminal block M2 powers the display backlighting (12 V). This wire does not have to be connected
for the wall-mounted Control Panel to work.
KEY TO WALL-MOUNTED CONTROL PANEL CONNECTIONS
A
Control Panel
B
Led interface accessory
B1
Base for wall-mounted Control Panel
(1)
Display backli12V
(2)
Earth connection
(3)
Power input/12V
For the wall-mounted Control Panel to work it must be configured (ambient probe and modulating flow temperature enabled).
8.1.1 PARAMETERS SETTING
ALL MODIFIED PARAMETERS SHOULD BE NOTED DOWN IN THE TABLE AT THE END OF THIS MANUAL.
KEY TO FIGURE MENU
1
Enduser
3
Engineer
2
Commissioning
4
OEM
The following procedure is used to access the four boiler
programming menus:
• from the main menu
C
.
•
A
and
C
(hold down for approx. 6 seconds)
B
menu
1
-
2
-
3
-
4
(see figure to side and key).
•
C
to go back one menu at a time to the main menu.
When the Control Panel is wall-mounted enable the
room
sensor
and
flow temperature modulation
as follows:
A) ROOM SENSOR
•
Access menu
2
.
•
B
Operator unit
B
to confirm.
•
B
programme row
40
(Used as)
B
.
•
B
(anti-clockwise)
Room unit 1
B
to confirm (the room sensor is now active).
•
C
to return to the previous menu then
B
Configuration
B
.
•
B
programme row
5977
(Function input H5) then
B
to confirm.
•
B
None
B
to confirm.
For correct operation of the environment unit during the reduced time band it is necessary to set the parameter 5977 = "none".
Summary of Contents for Sirius Three WH-130
Page 1: ...May 2018 Sirius three WH 130 150 kW ...
Page 10: ...7704679 01 3 08 18 10 583 892 600 G 1 1 2 G 1 1 2 G 1 198 100 100 100 102 CR_0775 95 223 24 ...
Page 20: ...7704679 01 3 08 18 20 WEATHER COMPENSATION CURVE GRAPHS QAC34 ...
Page 35: ...35 7704679 01 3 08 18 29 DIAGRAMS AGU 2 550 CR_0349 CR_0349 AVS 75 bis ...
Page 36: ...7704679 01 3 08 18 36 CG_2482 SAFETY THERMOSTAT Tmax 50 C free contact ...
Page 37: ...37 7704679 01 3 08 18 MODIFIED PARAMETERS Nr VALUE NOTE ...
Page 38: ...7704679 01 3 08 18 38 ...
Page 39: ...39 7704679 01 3 08 18 ...