REAR OR SIDE FLUEING - Page 6
FIG. 4 FLUE LENGTHS
MAXIMUM
LENGTH ‘X’
STANDARD FLUE
SYSTEM
510mm
(20in)
1 METRE FLUE
SYSTEM
955mm
(37in)
ELECTRICITY SUPPLY
A 240 volts ~ 50Hz, single phase electricity supply
fused to 3 amperes, must be provided in accordance
with the latest edition of the I.E.E. Wiring Regulations
and any other local regulations that may apply. The
current rating of the wiring to the boiler must exceed 3
amperes and have a cross sectional area of at least
0.75mm
2
in accordance with BS 6500. Table 16.
The supply to the boiler and its associated
equipment should be controlled by a 3A fused
double pole switch (having at least 3mm contact
separation in both poles) so that complete isolation
from the supply can be achieved to enable servicing
work to be carried out in safety.
TECHNICAL DATA - Page 6
Maximum working head
30.5m (100 ft)
Power consumption
80 watts
(excluding pump)
Minimum working head on
Fully Pumped systems
305mm (1 ft)
Flow/Return connection
28mm copper
Minimum circulating head
Gas supply connection
Rc. 1/2 (1/2 in BSP
on Gravity systems
1.2m (4 ft)
Female)
Gas supply pressure
20mbar
Water Content
6.5 litre (1.43 gal)
Maximum Flow temperature
82
º
C
Appliance Weight-installed
63.5kg (140 Ibs)
Electricity supply
240v ~ 50Hz fused
Appliance Weight-lift
54.5kg (120 Ibs)
at 3A
Internal Fuse
T1A