7.4.9 Guidance values for the gas flow rate
Tab.15 Guide values for the gas flow rate for natural gas
Model
Paramount
four 50
Paramount
four 60
Paramount
four 80
Paramount
four 95
Paramount
four 115
Nominal input (full load)
kW
50,0
58.0
77.0
95.0
115.0
Gas flow rate
l/min
l/min
l/min
l/min
l/min
7
119
138
183
226
274
7.5
111
129
171
211
256
8,0
104
121
160
198
240
Operating heating value
8.5
98
114
151
186
225
H
uB
in kWh/m
3
9,0
93
107
143
176
213
9.5
88
102
135
167
202
10
83
97
128
158
192
10.5
79
92
122
151
183
11
76
88
117
144
174
11.5
72
84
112
138
167
7.4.10 Guidance values for injector pressure
Tab.16 Guidance values for injector pressure (full load)
Model
Paramount four
30
Paramount four
40
Injector diameter for
Natural gas E (G20)
mm
4,90
7,80
LPG (propane)
mm
3,90
5,80
Guide values for injector pressure
G20 (15,0)
mbar
8,3 - 9,3
6.0 - 7.0
Propane
mbar
8,3 - 9,3
6.0 - 7.0
CO
2
-content: see reference below
(1) At pressure at end of boiler 0 mbar, 1013 hPa, 15 °C
(2) Values in brackets = Wobbe Index W
oN
in kWh/m
3
For more information, see
7.4.11 Guidance values for injector pressure
Tab.17 Guidance values for injector pressure (full load)
Model
Paramount
four 50
Paramount
four 60
Paramount
four 80
Paramount
four 95
Paramount
four 115
Injector diameter for
Natural gas E (G20)
mm
7,00
7.80
9.00
8.50
10.30
LPG (propane)
mm
5,80
6,20
7,20
6.50
7,40
Guide values for injector pressure
G20 (15,0)
mbar
7.2 - 8.2
6,5 - 7,5
8.0 - 9.0
13,0 - 14,0 13,0 - 14,0
Propane
mbar
6,8 - 7,8
7,0 - 8,0
8,1 - 9,1
15,0 - 16,0 15,0 - 16,0
7 Commissioning
7658013 - 02 - 15092016
Paramount four 30 – 115 kW
49