Prog. no.
Level Standard value
Type of charging
1: Recharging | 2: Full charging | 3: Full charging legio | 4: Full charg 1st time
day | 5: Full charg 1st time legio
5022
E
Full charging
Switching diff
5024
E
4 °C
Charging time limitation
5030
E
120 min
Discharging protection
0: Off | 1: Always | 2: Automatically
5040
E
Automatically
Discharg protec after charg
Off | On
5042
Off
Charging temp max
5050
E
69 °C
Recooling temp
5055
E
80 °C
Recooling collector
0: Off | 1: Summer | 2: Always
5057
E
Off
El imm heater optg mode
1: Substitute | 2: Summer | 3: Always
5060
E
Substitute
El immersion heater release
1: 24h/day | 2: DHW release | 3: Time program 4/DHW
5061
E
DHW release
El immersion heater control
1: External thermostat | 2: DHW sensor
5062
E
DHW sensor
Automatic push
Off | On
5070
E
On
Excess heat draw
Off | On
5085
E
On
With buffer
No | Yes
5090
E
Yes
With prim contr/system pump
No | Yes
5092
E
Yes
With solar integration
No | Yes
5093
E
Yes
Pump speed min
5101
E
0 %
Pump speed max
5102
E
100 %
Speed Xp
5103
E
15 °C
Speed Tn
5104
E
60 s
Speed Tv
5105
E
5 s
Transfer strategy
0: Off | 1: Always | 2: DHW release
5130
E
Always
Interm circ boost recharging
5139
E
5 °C
Intermediate circuit boost
5140
E
2 °C
Excess interm circ temp max
5141
E
2 °C
Flow setp compensation delay
5142
E
30 s
Flow setp compensation Xp
5143
E
50 °C
Flow setp compensation Tn
5144
E
30 s
Flow setp compensation Tv
5145
E
30 s
Full charging with B36
No | Yes
5146
E
No
Min start temp diff Q33
5148
E
-3 °C
Excess interm circ temp del
5151
E
30 s
(1) Parameters depend on the hydraulic System!
Configuration
Prog. no.
Level Standard value
Heating circuit 1
Off | On
5710
C
On
Heating circuit 2
Off | On
5715
C
Off
Heating circuit 3
Off | On
5721
C
Off
9 Settings
70
Paramount five 30 – 115