4.7 Chimney connection
The high-performance features of modern boilers and their use in
specific conditions as a result of the advance in burner technology
(e.g. first-stage or low modulation range operation) lead to very low
flue gas temperatures (<160°C).
For this reason:
- Use flue gas pipes designed to enable the flow of condensates
which may result from such operating modes in order to prevent
damage to the chimney.
- Install a draining tee at the bottom of the chimney.
The use of a draught moderator is recommended as well.
4.7.1
Flue size
Refer to applicable regulations while determining the size of the flue.
Please note that NXR5i boilers have pressurised and tight furnaces
and that the pressure at the nozzle must not exceed 0 mbar, unless
special sealing precautions have been taken, for instance in order to
connect a static condenser/regenerator.
4.7.2
Connection to the flue gas pipe
The connection shall be removable, and offer minimum load losses,
i.e. it must be as short as possible with no sudden change in section.
Its diameter shall always be at least equal to that of the boiler outlet,
i.e.: Ø 400 mm.
Boilers with 21 to 25 sections are supplied with a plain plate. The
maximum cut-out dimensions are 500 x 700 mm.
Fit a measuring point (Ø 10 mm hole) on the flue, in order to adjust
the burner (combustion check).
*Dimension representing the end of the 100 mm long chimney
connection.
Nota
: with models NXR5i-21, NXR5i-22, NXR5i-23,, NXR5i-24 and
NXR5i-25, a plain plate which must be cut out is supplied without the
100 mm chimney connection.
C003965-A
Boiler
NXR5i
-14
NXR5i
-15
NXR5i
-16
NXR5i
-17
NXR5i
-18
NXR5i
-19
NXR5i
-20
NXR5i
-21
NXR5i
-22
NXR5i
-23
NXR5i
-24
NXR5i
-25
Ø F
400
400
400
400
400
400
400
Plain plate
K
10
-19
-18
3
4
25
-24
-23*
-2*
-1*
20*
21*
Summary of Contents for NXR5i
Page 26: ...26 NXR5i 17 04 2012 300029103 001 01 PROVISOIRE Insulation 71 70 M000050 ...
Page 27: ...PROVISOIRE 27 17 04 2012 300029103 001 01 NXR5i Casing C001003 B ...
Page 33: ...PROVISOIRE 33 17 04 2012 300029103 001 01 NXR5i ...
Page 34: ...34 NXR5i 17 04 2012 300029103 001 01 PROVISOIRE ...
Page 35: ...PROVISOIRE 35 17 04 2012 300029103 001 01 NXR5i ...