CLEARANCES
The minimum boiler room clearances for access, erection and maintenance are given in Fig.2 and Fig.3, the
dimensions are minimum values. There is no minimum clearance above the boiler, however, it is recommended
that clearance is left above the top of the instrument panel to facilitate its removal. At the front of the boiler allow as
a minimum the A dimension, this is to allow access to the combustion chamber for maintenance and servicing. For
P dimension please refer to relevant burner card.
Fig.2 – Boiler Clearances
Minimum Clearance (Front)
Nu-Way Oil
Nu-Way Gas
Riello Oil
Riello Gas
EOGB Oil
EOGB Gas
Model
A (mm)
A (mm)
A (mm)
A (mm)
A (mm)
A (mm)
409
1580
1733
1555
1725
1807
1810
410
1580
1733
1555
1725
1807
1810
411
1580
1733
1600
1725
1807
1810
412
1580
1733
1600
1785
1807
1810
413
1542
1885
1610
1785
2086
2296
414
1542
1885
1610
1785
2086
2296
415
1542
2183
1610
2000
2086
2296
416
1686
2183
1950
2000
2086
2296
417
1686
2183
1950
2100
2086
2296
Fig.3 – Boiler Footprint/Base Details
No special plinth is required for
this boiler, a simple dry base is
sufficient. Boiler footprint and
base clearance details are given
in Fig.3.
700
500 min
P + 200
P
A
A
B
150mm x 6mm Flat
Plate (Not Supplied
by Potterton)
1070
450
409
410
411
412
413
414
415
416
417
A
1320
1460
1600
1740
1880
2020
2160
2300
2440
B
1540
1680
1820
1960
2100
2240
2380
2520
2660
Provision must be made to allow free movement of the boiler on
its base.
*NOTE: Base MUST NOT protrude from rear of boiler.
SECTION 1
POTTERTON COMMERCIAL PRODUCTS DIVISION
INSTALLATION, OPERATION & MAINTENANCE MANUAL
PAGE 4
NXR4