printed in usa
mFG. #8830045 - reV a
06/13
PAGE 2 OF 2
PVX-4Z-RM
VOICE EVACUATION
ACCESSORIES
Remote Microphone Panel:
Features
•
All-Call Remote Microphone
•
Overrides alarm tone and automatic message
•
Any number of remote microphones
•
Dead Front Cover Construction
•
Paging Microphone with Press to Talk Button
•
"In-Use" and "Fault" LEDs.
•
Supervised Wiring
•
May be located up to 5,000 feet away from Voice Evac Panel.
The PVX-RM is a supervised remote microphone for use with the
EVAX 25(50) voice evacuation system. The microphone provides
crystal-clear live voice messages over the system speakers.
Ideal for use when the fire alarm panels are in an electrical room, and
the annunciator and microphone
are in the lobby.
The PVX-RM is perfectly suited for applications in gymnasiums,
nightclubs, auditoriums, churches, and other places of assembly.
Locate at control rooms, guard stations, and reception areas.
Up to 5 PVX-RM Panels may be connected to a single PVX-SC
Supervisory Card. This provides supervision of the wires to the
PVX-RM and they may be located up to 5000 feet away.
Housed in an attractive surface or semi-flush mounted backbox, with a
hinged locking door. The PVX-RM features dead front
construction, a microphone with a “Press-to-Talk” button, and
discreet LEDs to display “In-Use” and “Fault” status.
Blackbox Dim:
8 x 10 x 3" (w x h x d)
Color:
Red (standard) Charcoal Grey (optional)
Operation
In the normal (Standby) mode, announcements can be made from any
remote microphone at any time. Simply keying any remote
microphone will allow a manual paging message to be broadcast in an
“ALL-CALL” mode.
If multiple remote microphones are used, and two or more are
simultaneously keyed, then the first microphone keyed will have
paging priority. The paging microphone in the master will always have
priority over any and all remote microphones. The PVX-RM can be
wired for general public address, and will be automatically disabled
on alarm.
In the alarm mode, the keying of any remote microphone will
interrupt any pre-recorded tone or message, and will allow manual
voice evacuation messages to take priority. When the microphone
Press-to-Talk key is released, the automatic pre-recorded voice
evacuation message (typically tone and voice) will be replayed from
the start.
In Use
Fault
Remote Microphone
PVX 25/50
Typical Application of Remote Microphone
5000 feet
Supervisory
Card
PVX-RM
PVX-SC
TB1
TB3
TB2
5
1
2
3
4
6
7
8
1
2
3
4
5
6
7
8
9
10
11
2 3 4 5 6 7 8
1
2 3 4 5 6 7 8
1
1
2
3
4
5
6
7
8
Normal
Alarm
Trouble
System Status LEDs
6 CONDUCTORS
SHIELDED