PSN-1000 & PSN 1000(E) 

Installation Manual

Document 5403599-Rev. C.-04/17

Summary of Contents for PSN 1000(E)

Page 1: ... Electric Signal Company LLC St Louis MO Customer Service 866 240 1870 Technical Support 866 956 1211 Fax 314 595 6999 www pottersignal com PSN 1000 PSN 1000 E Installation Manual Document 5403599 Rev C 04 17 ...

Page 2: ... AC 120VAC 50Hz 60Hz 5 1 AMP Min Low AC Detect 98VAC 240VAC 50Hz 60Hz 2 AMP Min Low AC Detect 194VAC Common Relays 3A 125VAC Resistive 3A 30VDC Resistive Battery Charging 27 3VDC 1A Low Battery Detect 20 4VDC Earth Fault to Any Terminal 0 Ohms Fuse Specification 8A 250VAC Time Lag I2 I1 NAC2 NAC1 NAC4 NAC3 NAC6 NAC5 IN A B P LINK OUT A B RPTR COMM MAIN COMM BULK COMM P LINK A B 120 240 VAC Jumper ...

Page 3: ...acid battery or equivalent The battery charging voltage is approximately 27 3 VDC and the circuit is supervised The battery circuit is protected with a non replaceable 7 amp poly switch located on the main circuit board The maximum battery charging circuit is 1 0 amp DC The battery circuit is rated for 8 to 55 AH batteries and the cabinet will house up to two 18 AH batteries The batteries will ope...

Page 4: ... the circuits is rated for a continuous 3 amps at 24 VDC The outputs are supervised and regulated The NACs reverse polarity upon activation and the board and illustrations are marked accordingly The NAC circuits can be configured for Class A operation Class A operation is accomplished by using a pair of NAC circuits Therefore the PSN 1000 can provide 3 Class A circuits each rated for a continuous ...

Page 5: ...tion Appliance I2 NAC 2 NAC 4 NAC Figure 3 Class B NAC The end of line resistor is a 5 1K ohm resistor The resistor assembly has been evaluated in past projects and is a standard in the Potter panel product line The Potter part number for the listed end of line assembly is 3005013 EOL Resistor Assembly ...

Page 6: ... Figure 4 Class A NAC Class A operation requires that two NAC circuits be utilized as shown in Figure 4 Up to 3 Class A circuits can be configured by pairing NAC 1 2 NAC 3 4 and NAC 5 6 I1 NAC 1 NAC 5 NAC Notification Appliance I2 NAC 2 NAC 4 NAC ...

Page 7: ...mum IDC voltage 24 VDC Maximum IDC current 15 ma The panel has ground fault detection on the input circuits The impedance to ground for ground fault detection is 0 ohms Figure 5 Input Circuit as Class B Dry Contact Input The end of line resistor is a 5 1K ohm resistor The resistor assembly has been evaluated in past projects and is a standard in the Potter panel product line The Potter part number...

Page 8: ...ovides an additional 1 amp at 24 VDC which can be used to power additional P Link devices such as LCD Annunciators and or SLC Loop expanders Wiring is fully supervised and power limited Any connection to ground of 0 ohms will be annunciated as a ground fault P Link Current 1 Amp Each P Link Voltage 24 VDC Maximum wire length 6 500 feet Maximum wire resistance Maximum wiring resistance is based on ...

Page 9: ...cation circuit and listed with the devices as outlined in Section 6 of this ULLD document The maximum current is 3 amps The maximum line impedance is calculated using the following formula Rmax ohm 24V Vmin 0 95V I total Vmin is the lowest voltage operation of the connected devices I total is the total current of the connected devices When a NAC is used as a releasing circuit the End of Line Diode...

Page 10: ...ction the circuit is power limited is supervised for open and short circuit conditions and provides a local energy connection Trip current NAC1 NAC6 3 Amps Max Voltage 24 VDC The panel has ground fault detection on municipal box connection circuits The impedance to ground for ground fault detection is 0 ohms Figure 10 NAC 1 NAC 5 NAC 3 A B NAC 2 NAC 4 NAC 6 A B P LINK Notes The EOL device shall be...

Page 11: ...osure Power limited wiring is to remain separated from non power limited by a minimum or 0 25 inches and all cabling should be insulated to the higher voltage When the panel is installed the National Electrical Code NEC NFPA 70 should be followed for the proper installation and separation of power limited and non power limited circuits The mixing of power limited and non power limited should be av...

Page 12: ...itch is provided for setting the ID of the PSN 1000 E An ID in the range of 1 31 can be specified according to the table below PSN 1000 E ID Dip Switch Settings SW 1 SW 2 SW 3 SW 4 SW 5 1 On Off Off Off Off 2 Off On Off Off Off 3 On On Off Off Off 4 Off Off On Off Off 5 On Off On Off Off 6 Off On On Off Off 7 On On On Off Off 8 Off Off Off On Off 9 On Off Off On Off 10 Off On Off On Off 11 On On O...

Page 13: ...l Use of another battery or not providing the proper clearance may result in a fire or an explosions The PSN 1000 is required to be installed in accordance with local and state building codes and NFPA 72 Na tional Fire Alarm Code The PSN 1000 and related system is required to be inspected and tested in accordance with NFPA 72 6 Compatibilities NAC Appliances Please refer to Potter document 5403592...

Page 14: ... Amps x 0 001 Refer to maximum allowable standby current Total A Total A 60 Minutes per Hour Alarm time minutes Multiply by standby hours ______ ______ Example 5 minute alarm Enter 12 10 minute alarm Enter 6 Total Standby AH Total Alarm AH Total Standby AH Total AH Efficiency Factor 0 80 Required AH Maximum Allowable Standby Current UL 24 Hour standby time 7 AH 230 A 18 AH 619 A 33 AH 1 151 A 55 A...

Page 15: ...ntact module 4 inch mount DCM 4 0 325 1 0 Monitored output module 4 inch mount MOM 4 Note 2 0 325 1 0 Twin relay module 4 inch mount TRM 4 0 325 1 0 Short circuit isolator SCI Note 3 0 325 2 34 Analog sounder base ASB 0 325 0 325 Analog relay base ARB 0 325 0 325 Isolator base AIB Note 3 0 325 2 34 SLC alarm LED Current n a n a n a 27 0 SLC Standby Current SLC Alarm Current Note 1 CIZM requires 24...