PAD300-SB
Addressable Sounder Base
8830221 - REV A
•
10/22
PAGE 1 OF 2
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
Description
The Addressable Sounder Base 6” (PAD300-SB) is a sounder base that
may be utilized in a variety of applications. The base has a locking
feature for the detector that may be used or removed in the field. Once
the detector is removed, the sounder is accessible in the bottom of the
unit.
The base has an independent sounder module that may be programmed
as a single station, zone or all call sounder. The PAD300-SB passes
through the sound pattern sent to the sounder, therefore it may
reproduce in any pattern the power supply provides.
The panel will support any combination of detectors or modules on
the SLC. The PAD300-SB does not consume an address on the loop
and is fully programmable to operate with any input. Once activated
the sounder will also follow the input from the power source and de-
activate accordingly.
Technical Specifications
SLC Voltage
24 VDC
SLC Standby Current
300 μA
PWR Voltage
16- 33 VDC
PWR Active Current
42mA
Alarm LED Current
1.4 mA
Sound Pressure
75dB @ 10ft per UL464
85dB @ 10ft per UL268
Installation Temperature Range
32 to 150°F (0°C to 66°C)
Operating Humidity Range
< 93% (Non-condensing)
Dimension
6.4 in (163 mm)
Weight
199 g (7.40 oz)
Height
1.57 in (40 mm)
Features
• Integrated Sounder in base
• UL464 and UL268 Listed
• Sounder independent of detector, allows for a single station,
grouped or all-call
• May be mapped to any device connected to the control panel
• Terminals accept 22 to 12 AWG wire sizes
• Supports Class A, Class X and Class B wiring
• Does not require SLC Loop address
• UUKL Listed for Smoke Control