Installation Manual: PAD200-DUCT Analog Addressable Duct Detector
NOTICE TO THE INSTALLER
This manual provides an overview and the installation instructions for the PAD200-DUCT module. This module is only compatible
with addressable fire systems that utilize the PAD Addressable Protocol.
All terminals are power limited and should be wired in accordance with the requirements of NFPA 70 (NEC) and NFPA 72 (National
Fire Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not operate as intended. For
further information, refer to the control panel installation instructions.
The module shall only be installed with listed control panels. Refer to the control panel installation manual for proper system
operation.
1. Description
The PAD200-DUCT duct smoke detector provides early detection of smoke and products of combustion present in the air moving
through HVAC ducts in commercial, industrial and residential applications. The PAD200-DUCT is designed and built to meet all
local requirements, as well as the NFPA regulations regarding duct smoke detectors.
Air sampling is accomplished by two tubes which protrude into the duct. An exhaust tube of one standard length (7") is supplied
in the installation kit with the smoke duct unit. Once the duct width has been determined, the air intake sampling tubes must be
ordered. Sampling tubes are supplied in three standard lengths: 2.5 ft., 5 ft., and 10 ft. and cut to size to fit the duct. Mounting
the duct smoke unit is accomplished by the use of a template and 2 sheet metal screws, which are provided. Mounting can be
achieved without the removal of the clear cover which is secured by 4 capture screws.
2. Setting the Address
All PAD protocol detectors and modules require an address prior to connection to the panel's SLC loop. Each PAD device's
address
(i.e., detector and/or module)
is set by changing the dip switches located on the device. PAD device addresses are
comprised of a
seven (7) position dip switch
used to program each device with an address ranging from 1–127.
Figure 1. PAD Device Dip Switch Addresses Table (Addresses 1
–
127)
Note:
Each
"gray" box
indicates that the dip switch is
"On,"
and each
"white" box
indicates
"Off."
Document 5406428-A 02/21
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: (800) 325-3936 • www.pottersignal.com
PAGE 1 OF 4
1 2 4 8 16 32 64
1 2 4 8 16 32 64
1 2 4 8 16 32 64
1 2 4 8 16 32 64
1 2 4 8 16 32 64
1
27
53
78
103
2
28
54
79
104
3
29
55
80
105
4
30
56
81
106
5
31
57
82
107
6
32
58
83
108
7
33
59
84
109
8
34
60
85
110
9
35
61
86
111
10
36
62
87
112
11
37
63
88
113
12
38
64
89
114
13
39
65
90
115
14
40
66
91
116
15
41
67
92
117
16
42
68
93
118
17
43
69
94
119
18
44
70
95
120
19
45
71
96
121
20
46
72
97
122
21
47
73
98
123
22
48
74
99
124
23
49
75
100
125
24
50
76
101
126
25
51
77
102
127
26
52
1 2 4 8 16 32 64
1 2 4 8 16 32 64
1 2 4 8 16 32 64
1 2 4 8 16 32 64
1 2 4 8 16 32 64