Potter PAD100-SPKB Quick Start Manual Download Page 3

8830143 - REV B

  •  

 

4/18

 PAGE 3 OF 3

Potter Electric Signal Company, LLC

      •   

 St. Louis, MO

      •   

 Phone: 800-325-3936 

      •   

 www.pottersignal.com

PAD100-SPKB

Speaker Base 

Model

Description

Stock No.

PAD100-SPKB

 Speaker Base

3992762

LFSBB-W

Speaker Base Back Box

3992761

Ordering Information

Wiring Diagrams

The  SLC  supports  NFPA  wiring  Class  B, A  and  X.  In  the  Class A 

arrangement,  two  separate  conductors  would  return  from  the  last 

detector base to a listed compatible Fire Alarm Control Panel (FACP). 

The  frequency  range  of  the  PAD100-SPKB  is  400-4000Hz  and  is 

suitable for line supervision.

Fig. 5

SPK

SLC

Adjust power taps using needle 

nose pliers.

PAD100-SPKB Field Selectable Power Tap Selection - Reverberant (dBA @ 10ft.)

Voltage

1/8 Watt

1/4 Watt

1/2 Watt

1 Watt

2 Watt

4 Watt

25 Volts

75.0 dBA

78.1 dBA

81.2 dBA

83.8 dBA

86.6 dBA 89.7 dBA

70.7 Volts

75.1 dBA

78.1 dBA

80.9 dBA

83.8 dBA

86.9 dBA 89.6 dBA

System Considerations

1. To select the proper wattage input for the speaker, move the jumper 

to the appropriate pin.
2. Always maintain electrical isolation between speaker and strobe 

wiring on combination units.

3. Do not exceed 130% of rated speaker voltage. If excessive distortion 

is heard, check amplifier for signal clipping. If clipping exists, reduce 

either amplifier input or gain.