 INSTALLATION MANUAL: IDC-6 INITIATING DEVICE CIRCUIT EXPANDER 

Before connecting a device to the RS-485 connection, take the following precautions to prevent potential damage to the 

RS-485 connection.
•  Power to the RS-485 connection is removed.

•  Field wiring on module is correctly installed.
•  Field wiring has no open or short circuits.

3.  TECHNICAL SPECIFICATIONS

P-Link Standby Current

20 mA

P-Link Alarm Current

20 mA

IDC PWR Standby Current

30 mA (maximum Standby)

IDC PWR Alarm Current

270 mA (maximum Alarm)

Input Zone Wiring Resistance

100 ohms max

Input Zone Capacitance

1 mF max

Input Zone Short Circuit Current 47 mA
Operating Temperature Range

32° to 120°F (0° to 49° C)

Operating Humidity Range

10%-93% (non-condensing)

Max no. of IDC-6 Expanders

31

Dimensions (WxHxD)

4" x 6" x 1 5/8"

Note:

  IDC PWR can be provided by any fire listed source.  Power must be 16 VDC- 33 VDC, and must be power limited.

4.  INSTALLATION

The IDC-6 is connected to the fire control panels using a 4-wire RS-485 connection. The connection is power limited 

and supervised. The IDC-6 must be mounted in either a compatible fire alarm panel, the PSN-1000, or within 20 feet of 

the panel or power supply using the AE-2, AE-8, or the AD-14 expander cabinet.   Each card is mounted to the exclusive 

Stacker Bracket for secure and accessible mounting.

The wiring diagrams shown below illustrate how to wire a IDC-6 as Class B and Class A.

FIGuRE 3. CLASS B P-LINK AND IDC POWER WIRING

Summary of Contents for IDC-6

Page 1: ...erflow or supervisory service The IDC 6 communicates via the PLink communication bus The IDC 6 can be mounted in either the control panel cabinet the intelligent power supply AE 2 AE 8 or the AE 14 expander cabinet Each card is mounted to the exclusive Stacker Bracket for secure and accessible mounting 2 SETTING THE ADDRESS Each P Link device has a five 5 position dip switch which is used to progr...

Page 2: ...one Capacitance 1 mF max Input Zone Short Circuit Current 47 mA Operating Temperature Range 32 to 120 F 0 to 49 C Operating Humidity Range 10 93 non condensing Max no of IDC 6 Expanders 31 Dimensions WxHxD 4 x 6 x 1 5 8 Note IDC PWR can be provided by any fire listed source Power must be 16 VDC 33 VDC and must be power limited 4 INSTALLATION The IDC 6 is connected to the fire control panels using ...

Page 3: ...ection and subsequently an open circuit These instructions do not purport to cover all the details or variations in the equipment described nor provide for every possible contingency to be met in connection with installation operation and maintenance Specifications subject to change without prior notification For Technical Assistance contact Potter Electric Signal Company at 866 956 1211 Actual pe...

Page 4: ... MB2WL A 25 ESL 611U S10 601U S00 25 611UD S10 601U S00 25 611UT S10 601U S00 25 612U S10 601U S00 25 612UD S10 601U S00 25 613U5 S10 601U S00 25 611UD S10 609U10 S00 25 612UD S10 609U10 S00 25 425C S10 N A N A 25 425CT S10 N A N A 25 HOCHIKI SLR 24 HD 3 HSC 221R HB 71 25 HSB 221 HB 54 25 HSB 221N HB 54 25 NS6 221 25 NS4 221 25 NS6 220 HB 3 25 SLR 24H HD 3 HSC 221R HB 71 25 HSB 221 HB 54 25 HSB 22...

Page 5: ... COMBINATION RETROFIT BASE ADAPTOR 70 501000 003 IDENTIFIER MAFE1 FOR SERIES 70 201000 BASES MODELS 001 002 003 AND 005 DUCT HOUSING WITH DETEC TOR BASE DN 51 IDENTIFIER DH22FE5 FOR CPD 7051 AND PSD 7155 DETECTORS ONLY DETECTOR MODEL Identifier Base Model Identifier Max No of Detectors Per Zone POTTER PS 24 HD 3 HOCHIKI SB 46 HB 71 HOCHIKI 25 HB 54 HOCHIKI 25 SB 93 HB 3 HOCHIKI 25 PS 24H HD 3 HOCH...

Reviews: