FFT-1000 INSTALLATION MANUAL-5409205-REV A  4/21

Main Supply Circuit

The AC terminals are located in the lower right hand portion of the main board.  The main board supervises the main 

AC power and provides indication that the AC power is absent.

Figure 2. Main Supply Circuit

The terminals are rated at 120 VAC/240 VAC 50/60 Hertz and are marked so accordingly on the board.  The earth 

ground connection is marked as “G” and is the furthest connection from the line voltage connection. 

The AC input power ratings: 

Maximum of 675 mA at the nominal 120 VAC rating.

Maximum of 80 mA at the nominal 240 VAC rating.

Rechargeable Battery Circuit

The battery charging circuit is provided in the bottom portion of the board. Terminal connections are provided to 

connect wire leads for battery connection. The battery must be a recognized or listed sealed lead acid battery or 

equivalent. 
The battery charging voltage is approximately 27.3 VDC and the circuit is supervised. The battery circuit is protected 

with a non-replaceable 7 amp poly switch located on the main circuit board. The maximum battery charging circuit is 

1.0 amp DC. 
The battery circuit is rated for 8 to 55 AH batteries and the cabinet will house up to two 18 AH batteries. The 

batteries will operate the panel for at least 24 hours and 5 minutes of alarm. To determine the minimum size batteries 

for standby and alarm times desired, the installer must complete a battery calculation work sheet to determine the 

minimum battery size for a particular application. For reference, the battery calculation work sheet is attached as 

Appendix A. Complete standby battery calculations must be completed to ensure adequate battery sizes are provided.

Summary of Contents for FFT-1000

Page 1: ...Installation Manual Document 5409205 Rev A 4 21 Potter Electric Signal Company LLC St Louis MO Customer Service 866 240 1870 Technical Support 866 956 1211 Fax 314 595 6999 For listing information vi...

Page 2: ...rcuit Voltage Type Power Type AC Connection High Voltage Non Power Limited Battery Connection Low Voltage Non Power Limited Trouble Relay High Voltage Non Power Limited Low AC Relay High Voltage Non P...

Page 3: ...to connect wire leads for battery connection The battery must be a recognized or listed sealed lead acid battery or equivalent The battery charging voltage is approximately 27 3 VDC and the circuit is...

Page 4: ...n must be for the higher voltage In the panel there are sufficient knock outs located around the periphery of the cabinet to allow the installer to maintain power limited and non power limited connect...

Page 5: ...6 500 feet Maximum wire resistance Maximum wiring resistance is based on load Calculate using the following equation Total P Link Alarm Current x Wire Resistance 6 volts Figure 5 P Link Class B and Cl...

Page 6: ...21 Figure 6 F Link Wiring Example AUX PWR The AUX PWR terminal provides an alternative option to power the FFT 1000 using a 24VDC external power source The AUX PWR input in unsupervised and power limi...

Page 7: ...d non power limited wiring on the main board as well as within the enclosure Power limited wiring is to remain separated from non power limited by a minimum or 0 25 inches and all cablings should be i...

Page 8: ...a system by adding the FFT EXP expansion module All phone circuits are shipped with a 5 1K EOL resistor The FFT 1000 is equipped with a proprietary P Link communication bus to operate in conjunction w...

Page 9: ...OFF 25 30 2 3 OFF OFF ON OFF 31 36 2 4 ON OFF ON OFF 37 42 2 5 OFF ON ON OFF 43 48 2 6 ON ON ON OFF 49 54 3 7 OFF OFF OFF ON 55 60 3 8 ON OFF OFF ON 61 66 3 9 OFF ON OFF ON 67 72 3 10 ON ON OFF ON 73...

Page 10: ...luminate green When AC is low or not detected the LED will disable GENERAL FAULT The general fault LED is off when no trouble s are indicated The LED will illuminate amber when an active trouble is pr...

Page 11: ...r 6 Class A phone circuits which are programmable and fully supervised The FFT 1000 can support up six 6 FFT EXP for Class B systems and fourteen 14 FFT EXP for Class A systems The FFT EXP communicate...

Page 12: ...Standby AH Total AH Efficiency Factor 0 80 Required AH Maximum Allowable Standby Current UL 24 Hour standby time 7 AH 215 A 18 AH 582 A 33 AH 1 082 A 55 AH 1 815 A Important Notes 1 FACP enclosure can...

Page 13: ...ociated LED on the FSB 24 will flash green indicating an incoming call By selecting the corresponding switch the LED will illuminate solid green indicating the call has been answered Mute When the MUT...

Reviews: