Technical Support: +44(0)23 9269 6638 (option 3) 

PAK200582_02B August 2016                        ©2016 ELMDENE INTERNATIONAL LTD  

 

S

PECIFICATION

 

 

 

Mains Input 

Rated Voltage 
(Operational voltage) 

110 – 240V ac  
(90 – 264V ac) 

Frequency 

50   Hz 

Input current 

< 1.0 Amps at full load 

Inrush current 

5A Max at 25 °C 110V ac for 10 ms 

Fuse 

T2.0 A 20mm, 250V ac HRC 

 

Output 

Voltage at full load 

 

Mains power 

 

Battery standby 

 
 

27.0 – 28.3V dc  (range) (27.6 V nominal) 

 

20.3 – 26.0V dc  

Ripple 

 

<200 mV pk – pk max @ Rated Voltage 

 

Fuse 
 

Load 

 

Battery 

 

F2.5 A 
F2.5 A 

Battery mode selected 

2.1 Ah

 

7 Ah

 

17/18 Ah 

(Link Fitted *)

 

Continuous Output Current 

No charging (Imax B) 

With charging  (Imax A) 

 

2.5 A 
2.0 A 

 

2.5 A 
2.0 A 

 

2.5 A 
1.8 A 

Battery Capacity 
e.g. 

-

 

PowerSonic model 

-

 

Yuasa model 

-

 

Interlogix model 

2 x 2.1 Ah 12 V 

 

PS12021 

NP2.1-12 

2 x 7 Ah 12 V 

 

PS12070 

NP7-12 

2 x 17/18 Ah 12 V 

 

PS12170 
NP17-12 

BS131N 

Battery Charging 

Constant current bulk charging to 80% capacity within 24 hours 
Float charging to 100% within 48 hours 
Eco charging and check every 24 hours  
– (for up to  4 hours charge, level dependent on temperature) 

Constant current charge 

0.3 A 

0.7 A 

Low battery threshold voltage 

23 V 

Deep discharge protection 

Threshold voltage – 21 V 

Quiescent current – no load 

< 30 mA @ 27.6 V 

Quiescent current – batt cut off 

< 1 mA @ 27.6 V 

* Default battery link setting = Fitted = 17/18Ah. 

 

 

Mechanical 

Product Reference 

STX2402-C 

STX2402-E 

Enclosure Dimensions 

 w x h x d (mm) 

275 x 330 x 80 

400 x 420 x 80 

Weight (kg)

 excluding battery 

3.3 Kg 

5.8 Kg 

Material  

1.2 mm steel white powder coated 

 

Environmental  

Temperature – Operating 

-10 to +40°C (operating) 75% RH non-condensing 

Temperature - Storage 

-20 to +80°C (storage) 

 

Summary of Contents for Elmdene STX2402-E

Page 1: ... fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an optional plug in serial interface that can provide diagnostic and fault reporting information to supervisory systems Certified by UL to EN54 4 1997 A1 A2 Up to 2A current to load at 27 6V dc nominal regulated output Charging capability to support 7 or 17 18Ah batteries Electronic over...

Page 2: ...odel Interlogix model 2 x 2 1 Ah 12 V PS12021 NP2 1 12 2 x 7 Ah 12 V PS12070 NP7 12 2 x 17 18 Ah 12 V PS12170 NP17 12 BS131N Battery Charging Constant current bulk charging to 80 capacity within 24 hours Float charging to 100 within 48 hours Eco charging and check every 24 hours for up to 4 hours charge level dependent on temperature Constant current charge 0 3 A 0 7 A Low battery threshold voltag...

Page 3: ... Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN Fault Present Blown fuses Battery fault Internal fault Investigate fault source using diagnostic LED Rectify fault where possible OPEN OPEN PSU Shutdown Mains lost Standby battery exhausted Restore ma...

Page 4: ...arm systems If the PSE is used as a power supply for Control and Indicating Equipment CIE the PSE shall be installed no further than 10cm from the CIE and close coupled by conduit This unit must be fed from a mains power source having a separate approved disconnect device and fitted with a fuse or other over current protection device rated at 5 A maximum Ensure that the disconnect device used has ...

Page 5: ...ded Ensure that wall fixings are appropriate to support this weight 7 The product should be mounted no further than 10 cm from the control and indicating equipment close coupled by conduit if it is being used to power the CIE directly 8 Fix to wall or other structure in correct orientation i e with hinge on left hand side using screws of sufficient size and length through the mounting holes 9 Prot...

Page 6: ...a disconnected battery 3 Disconnect the mains power Load Output and Remote Signalling 4 Connect the EPS and GEN PSU Fault outputs to the appropriate inputs of control equipment if remote fault monitoring is required 5 Connect the load output wiring as shown in Figure 3 Cable tie to saddle provided adjacent to exit hole Figure 3 Connections 6 Re apply mains Verify that the green Mains LED illuminat...

Page 7: ...7 Reconnect the mains Verify that the green Mains LED illuminates and the yellow Fault LED extinguishes 18 If connected verify that the EPS Fault monitor shows a closed contact and the GEN PSU Fault monitor shows a closed contact 19 Disconnect one of the battery leads ensuring that no exposed section of conductor or connector is allowed to contact exposed metal work other PSE terminals or other ba...

Page 8: ...an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries safely for onward transport to your supplier collection point or disposal facility Caution Risk of fire or explosion if bare battery wires are allowed to touch See Specification for battery type information The battery is marked with the crossed out wheelie bin symbol which m...

Reviews: