CS-24 AND CHS-24 PRODUCT INFORMATION

CS-24 & CHS-24 SERIES 

ANSI/UL & CAN/ULC COMPLIANT

CCS-24A, CCHS-24A, CCS-24B, CCHS-24B, 

CCS-24G, CCHS-24G CCS-24R, & CCHS-24R SERIES

ANSI/UL & CAN/ULC COMPLIANT

SELECTABLE CANDELA CEILING STROBE AND HORN/STROBE

I. INTRODUCTION

The Potter Electric Model CS-24, CHS-24, CCS-24A, CCHS-24A, CCS-24B, CCHS-24B, CCS-24G, CCHS-24G, CCS-24R, CCHS-24R strobe and horn/strobe, is a high quality visible or

audible/visible signaling appliance intended for ceiling applications.  The high intensity strobe utilizes a Xenon flash tube that generates a high-intensity flash visible from all angles.  This appliance

is intended to provide a visible or audible/visible, depending on the model, notification signal for the purpose of life safety and property protection. This appliance is ideal for any occupancy that

requires notification appliances per the applicable building or fire code or wherever dependable alarms are required.  The CS-24 and CHS-24 strobe is listed in compliance with ANSI/UL 1971,

Signaling Appliances for the Hearing Impaired. The CCS-24A, CCHS-24A, CCS-24B, CCHS-24B, CCS-24G, CCHS-24G, CCS-24R, CCHS-24R strobe is listed in compliance with ANSI/UL 1638,

Visual Signaling Appliances - Private Mode Emergency and General Signaling.

II. LOCATION

This appliance is intended for use in Fire Alarm Systems and is to be installed in accordance with this manual, the recommendation of the local authorities having jurisdiction, and other NFPA 

documents that provide standards on notification appliances for protective signaling systems.  The CS-24, CHS-24, CCS-24A, CCHS-24A, CCS-24B, CCHS-24B, CCS-24G, CCHS-24G, CCS-24R,

CCHS-24R is intended for indoor installations only.  This appliance is 

not

listed for 

outdoor

or drip proof applications.  Spacing for the CS-24 and CHS-24 shall be in accordance with Table A.  If a

room configuration is not square, the room size that will entirely encompass the room or subdivide the room into multiple squares shall be used.  

III. MOUNTING, ROUGH-IN BOX AND RUN WIRING

This unit is designed for mounting to most single gang boxes, 4" square outlet boxes, 2-gang masonry boxes or non-metallic 2-gang switch boxes.  Conduit entrance to boxes should be selected to

insure sufficient wiring clearance.

1. Run a minimum 18 gauge insulated 2 or more conductor cable.

2. Mount a box for each remote signaling appliance.  Screw bracket onto box. Insert signal into bracket and slide to the right firmly into the terminal block receptacle. Insert mounting screw as 

shown and tighten. Cover assembly with the plastic housing.

NOTICE:

WIRING SHOULD BE CONNECTED TO MOUNTING BRACKET PRIOR TO MOUNTING SIGNAL.  INCOMING POSITIVE POWER LEAD MUST BE BROKEN AND EACH LEAD IS TO

BE INSERTED INTO EACH OF THE TOP TWO TERMINALS. IF TWO POWER RUNS ARE MADE TO THE SIGNAL, ONE FOR THE STROBE AND ONE FOR THE HORN, ONLY ONE OF THE

RUNS MUST HAVE ITS POSITIVE LEAD BROKEN AND PLACED UNDER THE TWO SEPARATE TOP TERMINALS. A BARRIER IS PROVIDED TO PREVENT BOTH LEADS FROM BEING

PLACED UNDER THE SAME TERMINAL

.

Table A 

NOTICE

: THE VISUAL SIGNAL MUST BE IN THE DIRECT VIEWING AREA OF THE OCCUPANT IN ORDER

TO BE SEEN.

Strobe light can not be seen when objects such as doors, furniture or walls block

strobe light.

NOTICE:

VISUAL SIGNALS FOR THE HEARING IMPAIRED ARE ONLY ONE METHOD OF ALERTING THE

HEARING IMPAIRED.  VISUAL SIGNALS MAY NOT BE THE PREFERRED METHOD FOR NOTIFYING ALL

HEARING IMPAIRED INDIVIDUALS.

NOTICE:

THE STROBE LIGHT MUST BE SEEN BY THE SLEEPING PERSON.  IF THE PERSON HAS HEAD

TURNED OR OTHERWISE UNABLE TO BE ALERTED BY VISUAL, THE STROBE WILL NOT BE EFFECTIVE.

CAUTION: 

Strobe light must be installed within 16

feet of the pillow when used in a sleeping area.

550-0594

Page 1

Room Spacing for Ceiling-Mounted Visible Appliances per NFPA 72, 2013 Edition

Minimum Required Light Output (Effective Intensity, Cd; One Light)

Maximum Room Size

Maximum Ceiling Height

Meters

Feet

10 Foot Ceiling

20 Foot Ceiling

30 Foot Ceiling

6.10 x 6.10

20 x 20

15

30

55

9.14 x 9.14

30 x 30

30

45

75

13.4 x 13.4

44 x 44 

75

75

NA

15.2 x 15.2

50 x 50

NA

NA

95

NOTICE

: DC VOLTAGE RANGE LIMITS: 16-33V.  FWR VOLTAGE

RANGE LIMITS: 16-33V.  THIS PRODUCT WAS ONLY TESTED TO

THE STATED VOLTAGE RANGE(S); DO NOT APPLY 80% AND

110% OF THIS RANGE FOR SYSTEM OPERATION.

CLEAR Lens Strobe Current Ratings

Use with CS-24 & CHS-24 Products

Candela

Regulated 24VDC Max.

Operating Current (mA)

Regulated 24VFWR Max.

Operating Current (mA)

24VDC Nominal

Operating Current (mA) 

15

120

190

97

30

120

191

97

75

200

277

143

95

220

298

148

115

290

418

201

150

321

427

205

ADDITIONAL CAN/ULC LISTED PRODUCT INFORMATION IS FOUND ON PAGE 4

NA = Not allowable

firealarmresources.com

Summary of Contents for CS-24 Series

Page 1: ...wiring clearance 1 Run a minimum 18 gauge insulated 2 or more conductor cable 2 Mount a box for each remote signaling appliance Screw bracket onto box Insert signal into bracket and slide to the right firmly into the terminal block receptacle Insert mounting screw as shown and tighten Cover assembly with the plastic housing NOTICE WIRING SHOULD BE CONNECTED TO MOUNTING BRACKET PRIOR TO MOUNTING SI...

Page 2: ...ed to power and synchronize the horn place switches 1 and 2 in the OFF position on the CHS 24 CCHS 24A CCHS 24B CCHS 24G CCHS 24R w Choose either continuous horn and allow the FACP to control the horn or choose temporal horn and synchronize the horns with the Potter Electric AVSM synchronization protocol w Use the Potter Electric AVSM synchronization protocol to provide synchronization and mute th...

Page 3: ...e fire detection units in the system All auxiliary signals should be activated 4 An operational test on this product should be conducted in accordance with National Standards or at a minimum annually and more often if dictated by local and state codes or authorities having jurisdiction NOTICE THESE TESTING PROCEDURES AND TROUBLESHOOTING INSTRUCTIONS ARE GENERALIZED PLEASE REFER TO THE SYSTEM CONTR...

Page 4: ...ship and materials under normal use and service This warranty does not apply and is void if damage or failure is caused by accident abuse misuse abnormal use faulty installation liquid contact fire earthquake or other external cause operating the appliance outside Potter Electrical Signal Company LLC s published guidelines or service alteration maintenance or repairs performed by anyone other than...

Page 5: ...le brancher dans la prise du réceptacle Mettre la vis de montage comme illustré puis la serrer Recouvrir l ensemble du boîtier de plastique AVIS LES FILS DOIVENT ÊTRE BRANCHÉS AU SUPPORT AVANT D Y POSER L APPAREIL DE SIGNALISATION LE FIL D ALIMENTATION POSITIF DOIT ÊTRE SCINDÉ EN DEUX CHAQUE PARTIE ÉTANT INSÉRÉE DANS LES DEUX BORNES SUPÉRIEURES SI DEUX FILS D ALIMENTATION SONT ACHEMINÉS À L APPARE...

Page 6: ...ilisation de l avertisseur dans ce mode et à cette tension n atteint pas le niveau sonore minimum de la norme ANSI UL 464 exigé pour la sécurité incendie publique Ces paramètres conviennent uniquement à une utilisation de l appareil de signalisation pour la sécurité incendie privée Pour les applications publiques utiliser les paramètres dBA les plus élevés Niveaux sonores dB de l avertisseur Pièce...

Page 7: ...en faire le suivi w S assurer que les cavaliers et les commutateurs sont correctement configurés dans le module de commande et dans les appareils de signalisation Si le cavalier du module AVSM est débranché les avertisseurs ne produiront aucun son à moins qu une entrée soit fournie aux bornes H et H du module de commande 3 Pour vérifier les appareils de signalisation déclencher le panneau auxiliai...

Page 8: ... emballer soigneusement l appareil pour réduire au minimum les risques de dommage pendant le transport Si nous recevons un appareil endommagé en cours de transport nous vous en aviserons et il vous reviendra d obtenir dédommagement de la part du transporteur Si vous transmettez une demande valable à Potter Electrical Signal Company LLC pendant la période de garantie Potter Electrical Signal Compan...

Reviews: