Potter 2020230 Installation, Operation And Instruction Manual Download Page 8

8

EVD-1 • 5401043 • REV M • 9/07

Recommended Control Panel Wiring and
Remote Test and Annunciator Connections
Figure 3a

Installation

The EVD-1 System must be installed in 
accordance with all applicable local codes.

1. 

Mount EVD-1 controller and wire 
according to Figures 2 and 3a.                     

2. 

Refer to Figures 2a and 3a for connection of 
a remote test annunciator, RTA, and/or a UL 
listed central station test unit, if applicable.

3. 

Refer to Figures 2 and 3a for the connection 
of UL listed dry contacts, if applicable.

4. 

Wire control unit connections and apply 12 
VDC to the EVD-1 system.

5. 

See Figures 3b & 3c for 4 or 6 wire 
installation wiring.

6. 

High Security "B" cable and connections to 24 
hour alarm  zone as shown are UL requirements 
for UL Safe Complete installations.

SAFE 

DETECTOR 

ZONE

24 HOUR 

ALARM 

ZONE

DRAIN WIRE FOR OUTER SHIELD

DRAIN 
WIRE FOR 
INNER 
SHIELD

HIGH SECURITY CABLE

BLACK

-

RED

+

12 VOLT DC

SUPPLY

+

-

MODEL EVD-1

CONTROL UNIT END OF 

LINE RESISTORS

MODEL RTA

RED 

ALARM 

LED

YELLOW 

TAMPER 

LED

TEST SWITCH

CURRENT 

LIMITING 

RESISTOR

(a)

WITHOUT SAFE 

CONTACT

SAFE 

CONTACTS

MODEL EVD-1

CONTROL UNIT END OF 

LINE RESISTORS

SAFE 

DETECTOR 

ZONE

BLACK

-

RED

+

12 VOLT DC

SUPPLY

+

-

MODEL RTA

RED 

ALARM 

LED

YELLOW 

TAMPER 

LED

TEST SWITCH

CURRENT 

LIMITING 

RESISTOR

DRAIN WIRE FOR OUTER SHIELD

DRAIN 
WIRE FOR 
INNER 
SHIELD

HIGH SECURITY CABLE

24 HOUR 

ALARM 

ZONE

(b)

WITH SAFE

CONTACT

(a)

(b)

EVD-1

EVD-1

1

1

4

7

2

2

2

2

8

8

6

3

5

9

Figure 2  Recommended Wiring EVD-1 Controller

Summary of Contents for 2020230

Page 1: ...troller RTA optional Manual 5401043 Rev N 6 09 EVD 1 Electronic Vibration Detector System Installation Operation and Instruction Manual All specifications subject to revision DWG 516 933 4900 dwgdistribution com ...

Page 2: ... determines that said product is not operating properly as a result of causes other than defective manufacture labeling or packaging The Aforesaid Warranty Is Expressly Made In Lieu Of Any Other Warranties Expressed Or Implied It Being Understood That All Such Other Warranties Expressed Or Implied Including The Warranties Of Merchantability And Fitness For Particular Purpose Are Hereby Expressly E...

Page 3: ...m Zone 9 EVD Wiring with Safe Detector Zone Only 10 Sensitivity Adjustments 11 Analog Test Point Levels 11 Testing 11 Safe Construction Requirements 11 Recommended Detector Locations 12 Determining the Number of Detectors for a Safe Application 12 Determining the Maximum Linear Distance on a Safe 13 Typical Safe Exterior Dimensions and Maximum Linear Distances 13 Typical UL Complete Safe Installat...

Page 4: ...4 EVD 1 5401043 REV M 9 07 ...

Page 5: ...0cm D Weight 0 64 lbs 0 29 kg Enclosure Base Die cast aluminum Cover Stamped Steel 22 Gauge Power Input 9 0 VDC to 16 0 VDC 12 VDC Nominal Maximum 0 1 V ripple Typical Current Supply Voltage 12 0 VDC Normal Standby Condition 26 mA Alarm Condition 24 mA Tamper Condition 34 mA With model RTA connected add 10 mA in Tamper Condition and 10 mA in Alarm condition Maximum Current Supply Voltage 16 0 VDC ...

Page 6: ...g of the installation The EVD 1 contains a multi color LED to indicate system status This status LED indicates three states Notes 1 If both an alarm condition and a tamper alarm condition exist the status LED will indicate RED for the alarm The remote annunciators and the alarm and tamper alarm contacts will indicate both alarm and tamper alarm conditions 2 If the microprocessor fails the status L...

Page 7: ...ing should be as specified in Table 1 or with UL listed equivalents 1 Cable clamp knockout locations are shaded Be sure to remove clamp from base and to cleanly knock out cable openings in the cable clamp before feeding wire through the clamp 2 Connections to UL listed control unit via UL listed high security cable See Table 1 See Figure 3b 3c for 4 or 6 wire installation wiring 3 Connections to r...

Page 8: ...wiring 6 High Security B cable and connections to 24 hour alarm zone as shown are ULrequirements for UL Safe Complete installations SAFE DETECTOR ZONE 24 HOUR ALARM ZONE DRAIN WIRE FOR OUTER SHIELD DRAIN WIRE FOR INNER SHIELD HIGH SECURITY CABLE BLACK RED 12 VOLT DC SUPPLY MODEL EVD 1 CONTROL UNIT END OF LINE RESISTORS MODEL RTA RED ALARM LED YELLOW TAMPER LED TEST SWITCH CURRENT LIMITING RESISTOR...

Page 9: ...9 EVD 1 5401043 REV M 9 07 Recommended Control Panel Wiring With Safe Detector Zone And 24 Hour Alarm High Security B Cable Required For UL Safe Complete Installations Figure 3b DWG 1043 10 ...

Page 10: ...10 EVD 1 5401043 REV M 9 07 Optional Control Panel Wiring With Safe Detector Zone Only 4 Conductor Shielded Cable Required Figure 3c ...

Page 11: ... by the status LED turning AMBER If the system is in alarm when a tamper condition occurs the status LED will remain RED identifying the alarm condition The tamper alarm remote annunciator and the tamper alarm contact always identify a tamper condition Testing Applying a magnet to the side of the EVD 1 controller see Figure 1 actuates a magnetic switch and generates a test signal The EVD 1 activat...

Page 12: ...d detector location s of a safe application with double doors Multiple Detector Applications When more than two detectors are required on a safe mount the first two detectors as recommended for a two detector application Mount the remaining detectors on the remaining surfaces centered and spaced evenly to ensure complete detector coverage Alternately mount a detector centrally on the safe door and...

Page 13: ...Example h 62 w 55 d 29 1 Compute X1 h w 1 X1 62 55 X1 117 2 Compute X2 2d w 2 X2 2 x 29 55 X2 113 3 Find X minimum X1 X2 3 X 113 4 Compute J w d4 J 55 29 J 84 5 Find D maximum X J 5 D 113 Where h Safe Height w Safe Width d Safe Depth D Maximum Linear Distance This rule of thumb is valid for most available safe sizes However if any one dimension is very large or very small when compared to the othe...

Page 14: ...power for mercantile alarms and 72 hours of standby power for bank vault alarms Typical UL Complete Vault Installations 1 Install in accordance with Underwriter Laboratories standard UL 681 2 Install EVD 1 detectors on interior walls ceilings and floors spaced as shown in Figure 7 Refer to Table 6 for maximum spacing on various materials 3 A detector must be installed on the vault door if the net ...

Page 15: ... Coverage Steel plates at least 1 4 thick Minimum 8 0 11 3 x 11 3 8 x 13 9 10 x 12 5 15 x 5 6 Half 15 0 21 2 x 21 2 8 x 28 9 10 x 28 3 15 x 26 20 x 22 4 Maximum 20 0 28 3 x 28 3 8 x 39 2 10 x 38 7 15 x 37 1 20 x 34 6 Monolithic concrete at least 6 thick Minimum 16 0 22 6 x 22 6 8 x 31 0 10 x 30 4 15 x 28 3 20 x 25 0 Concrete block at least 6 thick Minimum 16 0 22 6 x 22 6 8 x 31 0 10 x 30 4 15 x 2...

Reviews: