MFG. #5400928 - REV D

 1/08  

PRINTED IN USA

 PAGE 3 OF 3

MODEL PS10

PRESSURE SWITCH

Break out thin section of divider to provide path for wires 
when wiring both switches from one conduit entrance.

One Conduit Wiring

Fig. 7

Fig. 9

Removing Knockouts

W/ PRESSURE APPLIED

W/O PRESSURE APPLIED

NC

NO

C

C                       1                        2

NC

NO

C

C                       1                        2

Changing Pressure

Fig. 8

•Installation must be performed by qualifi ed personnel and in 
 accordance with all national and local codes and ordinances. 
•Shock hazard. Disconnect power source before servicing.
 Serious injury or death could result. 

 

 

 

•Read all instructions carefully and understand them before     
 starting installation. Save instructions for future use. Failure to  
 read and understand instructions could result in improper  
 operation of device resulting in serious injury or death.
•Risk of explosion. Not for use is hazardous locations. Serious   
 injury or death could result.

•Do not tighten by grasping the switch enclosure. Use wrenching   
 fl ats on the bushing only. Failure to install properly could damage   
 the switch and cause improper operation resulting in damage to  
 equipment and property. 

 

 

 

 

•To seal threads, apply Tefl on tape to male threads only.  Using  
 joint compounds or cement can obstruct the pressure port inlet   
 and result in improper device operation and damage to equipment. 
•Do not over tighten the device, standard piping practices apply.

Engineer/Architect Specifi cations Pressure Type 
Waterfl ow Switch 

Pressure type waterfl ow switches; shall be a Model PS10 as 
manufactured by Potter Electric Signal Company, St Louis MO., 
and shall be installed on the fi re sprinkler system as shown and or 
specifi ed herein.
Switches shall be provided with a ½” NPT male pressure connection 
and shall be connected to the alarm port outlet of; Wet Pipe Alarm 
Valves, Dry Pipe Valves, Pre-Action Valves, or Deluge Valves. The 
pressure switch shall be actuated when the alarm line pressure reaches 
4 - 8 PSI (0,27 - 0,55 BAR).
Pressure type waterfl ow switches shall have a maximum service 
pressure rating of 300 PSI (20,68 BAR) and shall be factory adjusted 
to operate on a pressure increase of 4 - 8 PSI (0,27 - 0,55 BAR)

Pressure switch shall have one or two form C contacts, switch contact 
rating 10.1 Amps at 125/250 VAC, 2.0 Amps at 30 VDC.
Pressure type waterfl ow switches shall have two conduit entrances 
one for each individual switch compartment to facilitate the use of 
dissimilar voltages for each individual switch.  

The cover of the pressure type waterfl ow switch shall be Zinc die-cast 
with rain lip and shall attach with one tamper resistant screw. The 
Pressure type waterfl ow switch shall be suitable for indoor or outdoor 
service with a NEMA 4/IP55 rating.
The pressure type waterfl ow switch shall be UL Ulc and CSFM listed,  
FM and LPC approved and NYMEA accepted.

For low pressure use: 
Com and Terminal 1

For waterfl ow use: 
Com and Terminal 2

Summary of Contents for 1340103

Page 1: ...or or outdoor when used with NEMA 4 conduit fittings Temperature range 40 F to 140 F 40 C to 60 C Service Use Automatic Sprinkler NFPA 13 One or two family dwelling NFPA 13D Residential Occupancy up to four stories NFPA 13R National Fire Alarm Code NFPA 72 Potter Electric Signal Company 2081 Craig Road St Louis MO 63146 4161 Phone 800 325 3936 Canada 888 882 1833 www pottersignal com into alarm po...

Page 2: ...TER MOTOR GONG DWG 923 2AA Fig 2 Fig 4 Fig 5 Fig 3 NOTE To prevent leakage apply Teflon tape sealant to male threads only ADJUSTMENT KNOB 2 87 72 97 4 22 107 19 2 48 62 87 3 78 95 89 3 20 81 28 1 60 40 64 Fig 1 GROUND SCREWS 1 2 NPT An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections The wire must be severed thereby providing ...

Page 3: ...evice standard piping practices apply Engineer Architect Specifications Pressure Type Waterflow Switch Pressure type waterflow switches shall be a Model PS10 as manufactured by Potter Electric Signal Company St Louis MO and shall be installed on the fire sprinkler system as shown and or specified herein Switches shall be provided with a NPT male pressure connection and shall be connected to the al...

Page 4: ...AC 2 0 Amps at 30VDC One SPDT in PS40 1 Two SPDT in PS40 2 Environmental Specifications NEMA 4 IP55 Rated Enclosure indoor or outdoor when used with NEMA 4 conduit fittings Temperature range 40 F to 140 F 40 C to 60 C Tamper Cover incorporates tamper resistant fastener that requires a special key for removal One key is supplied with each device For optional cover tamper switch kit order Stock No 0...

Page 5: ...ESSURE DROP WITH NORMAL SYSTEM PRESSURE APPLIED HIGH TERMINAL 1 WILL CLOSE ON PRESSURE INCREASE GROUND SCREWS 1 2 NPT NOTE To prevent leakage apply teflon tape sealant to male threads only ADJUSTMENT KNOB 2 87 72 97 4 22 107 19 2 48 62 87 3 78 95 89 3 20 81 28 1 60 40 64 Fig 4 An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connection...

Page 6: ...units shall have a maximum pressure rating of 300 PSI 20 68 BAR and shall be adjustable from 10 to 60 PSI 0 7 to 4 1 BAR Pressure switches shall have two conduit entrances one for each individual switch compartment to facilitate the use of dissimilar voltages for each individual switch The cover of the pressure switch shall be zinc die cast with rain lip and shall attach with one tamper resistant ...

Page 7: ...itch Contacts Two SPDT Form C 10 1 Amps at 125 250VAC 2 0 Amps at 30VDC Environmental Specifications NEMA4 IP55RatedEnclosure indoororoutdoorwhen used with NEMA 4 conduit fittings Temperature range 40 F to 140 F 40 C to 60 C Tamper Cover incorporates tamper resistant fastener that requires a special key for removal One key is supplied with each device For optional cover tamper switch kit order Sto...

Page 8: ...ELL COM 1 2 COM 1 2 EOLR TO FIRE ALARM PANEL POSITIVE DC OR HOT AC NEGATIVE DC OR NEUTRALAC LINE LOAD OPEN CIRCUIT CLOSES ON ALARM RING A LOCAL BELL WITH NORMAL SYSTEM PRESSURE APPLIED TERMINAL 2 CLOSES ON PRESSURE DROP An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections The wire must be severed thereby providing supervision o...

Page 9: ...tructions for future use Failure to read and understand instructions could result in improper operation of device resulting in serious injury or death Risk of explosion Not for use is hazardous locations Serious injury or death could result Do not tighten by grasping the switch enclosure Use wrenching flats on the bushing only Failure to install properly could damage the switch and cause improper ...

Page 10: ...rm C 10 1 Amps at 125 250VAC 2 0 Amps at 30VDC One SPDT in PS120 1 Two SPDT in PS120 2 Environmental Specifications NEMA 4 IP55 Rated Enclosure indoor or outdoor when used with NEMA 4 conduit fittings Temperature range 40 F to 140 F 40 C to 60 C Pressure Range 25 175 PSI 1 7 12 1 BAR Differential Typical 2 lbs at 25 PSI 0 14 at 1 7 BAR 8 lbs at 175 PSI 55 at 12 1 BAR Maximum System Pressure 300 PS...

Page 11: ...RE PUMP OS Y VALVE WATER BY PASS TEST VALVE RBVS DWG 926 1A Typical Connections COM 1 2 EOLR TO FIRE ALARM PANEL TO FIRE ALARM PANEL EOLR COM 1 2 2 1 COM HIGH AIR LOW AIR PS120 1 PS120 2 WITH NORMAL SYSTEM PRESSURE APPLIED LOW TERMINAL 2 CLOSES ON PRESSURE DROP WITH NORMAL SYSTEM PRESSURE APPLIED HIGH TERMINAL 1 WILL CLOSE ON PRESSURE INCREASE GROUND SCREWS 1 2 NPT NOTE To prevent leakage apply te...

Page 12: ... 0 7 BAR from normal If two switches are provided the second switch shall be set to operate at a pressure increase of 10 PSI 0 7 BAR from normal Switch contact shall be rated at 10 1Amps at 125 250VAC and 2 0Amps at 30VDC The units shall have a maximum pressure rating of 300 PSI 20 68 BAR and shall be adjustable from 25 to 175 PSI 1 7 to 12 1 BAR Installation must be performed by qualified personn...

Page 13: ...13D Residential occupancy up to four stories NFPA 13R National Fire Alarm Code NFPA 72 Tamper Cover incorporates tamper resistant fasteners that require a special key for removal One key is supplied with each device For optional cover tamper switch kit order Stock No 0090018 Potter Electric Signal Company 2081 Craig Road St Louis MO 63146 4161 Phone 800 325 3936 Canada 888 882 1833 www pottersigna...

Page 14: ...terial may obstruct pressure aperture resulting in loss of alarm signal Device must be installed before any shut off valve on alarm port line unless it is supervised by a supervisory switch such as Potter Model RBVS The system should be tested on a quarterly basis or more frequently to insure proper operation Due to the possibility of unintended discharges caused by pressure surges trapped air or ...

Page 15: ...10 EXF into alarm port piping extending from alarm check valve Retard provisions are not required Insure that no shut off valves are present between the alarm check valve and the PS10 EXF Testing Accomplished by opening the water by pass test valve or the inspector s end of line test valve When using end of line test allow time for excess pressure to bleed off Dry System Connect the PS10 EXF into ...

Page 16: ...EXF inoperative To comply with NFPA 72 any such valve shall be electrically supervised with a supervisory switch such as Potter Model BVS An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections The wire must be severed thereby providing supervision of the connection in the event that the wire becomes dislodged from under the termi...

Page 17: ...ter Electric Signal Co of St Louis Mo U S A and shall be installed on the sprinkler systems as shown on the drawings and or as specified herein Switches shall be provided with a 1 2 NPT male pressure connection to be connected into the air supply line on the system side of any shut off valve A Model BVL bleeder valve as supplied by Potter Electric Signal Co of St Louis Mo U S A or equivalent shall ...

Page 18: ...lation of a Potter Bleeder Valve Model BVL in the line to the PS40 EXF CENELEC DEMKO NO D 03 Atex 0311298 EN50018 EN50014 FM Approved Dimensions 152mm Dia x 178mm H Enclosure Cast aluminum Pressure Connection 1 2 NPT male brass fitting Conduit Entrance 1 2 NPT female conduit opening Factory Adjustment One switch operates on decrease at 207 kPA 2 07 BAR 30 PSI and one switch operates on increase at ...

Page 19: ...h switch changes with pressure increase Low switch changes with pressure decrease An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections The wire must be severed thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal Typical Electrical Connections ...

Page 20: ...re permitted in the area To reduce the risk of ignition of hazardous atmospheres disconnect supply circuits before opening cover Keep cover tight while circuits are live Cover screws must be torqued to a minimum of 2 N m Engineer Architect Specifications Air pressure supervisory switch shall be a Model PS40 EXF as manufactured by Potter Electric Signal Co of St Louis Mo U S A and shall be installed...

Page 21: ...stings Approvals UL Standard 508 Guide NKPZ and CSA Standard C22 2 No 14 M Class 321106 for Pressure Operated Industrial Control Equipment UL Standard 873 Guide XAPX and CSA Standard C22 2 No 24 Class 481302 for Temperature Indicating and Regulating Equipment CE Marked Ambient Media Temperature Range 4 F to 180 F 20 C to 82 C Construction NEMA Type 4X enclosure for indoor or outdoor use To maintai...

Page 22: ...ed settings are obtained replace the adjustment cover The adjustment cover and enclosure cover can be made tamper resistant by a single sealing wire inserted through the hole in the locking bar The repeatability of the set and reset points is typically 1 of the operating range Ordering Information Stock Number Model Number Adjustable Operating Range Minimum Deadband Proof Pressure Pressure Connect...

Page 23: ...n set and reset points may be obtained at any point in the operating range of the switch When the pressure drops below the setting a snap action switch closes energizing the built in pump control relay and turns the pump on When the pressure increases above the high setting the snap action switch opens de energizing the built in pump control relay and turns the pump off This control device is desi...

Page 24: ...edbymanuallyactuatingtheswitch actuator on the side of the snap action switch inside the enclosure See Fig 3 and metering for 120V AC between the red and white wires Fig 3 Adjustments Thetwothumbadjustmentdials accessiblethroughtheenclosurecover are usedtoadjustthesetpointandresetpointoftheswitch Thedialscalesand pointer may be used to give an indication of the low and high set points The high set...

Page 25: ...mal system air pressure of 30 PSI Alarm indication One normally open contact that closes if the pressure drops at a rate of 1 PSI 007 BAR per second or greater indicates an open sprinkler head normal response time is approximately 2 seconds or if the pressure drops to 5 5 PSI 38 UL Listed Extinguishing System Attachment 354L Accelerator 456A U S Patent Number 5 971 080 Stock number 1341300 BAR The...

Page 26: ...e QRS PFC 4410 RC Splices shall not be permitted If an 8 conductor shielded cable is not available multiple cables may be used to provide the number of conductors required providing all cables are shielded 2 All wiring between the QRS and PFC 4410 RC shall be installed in a continuous run of metal conduit Interruptions in the continuity of the metal conduit shall not be permitted There shall not b...

Page 27: ...oblem The system false trips or other unexplained operations Check Was shielded cable used Check Istheentirelengthofshieldedcablecompletelyenclosedinmetalconduit Check IsthedrainwireconnectedtotheSterminalofthePFCseriespanelonly Check Make sure the drain wire is not connected to the QRS Check Make sure the cover is installed on the QRS Check Make sure no wires other than the shielded cable for the...

Page 28: ...onnect any otherinitiatingdevicetoanyinitiatingzoneofthePFC 100RC Doing so could result in unintended operation of the dry pipe system The QRS uses electronic components to monitor the air pressure Keep all radio transmitters or RF sources at least ONE foot from the QRS Failure to do so could result in unintended operation of the dry pipe system ...

Reviews: