Popp POPE009204 Manual Download Page 3

The process for button 1 and 2 is indicated with fast red/green blinking, the process for button 3 and 4 shows a fast green blinking. Every button push stops the
process. This fast inclusion only works when device is in factory default.

Attention:

 For convenience reasons some special short cut apply IF and only 

IF the KFOB is the primary controller of the network

: The 

first device included

into a button group will define the commands sent

 out by this group regardless of the default value of the configuration parameters 11-14. If the device is a

door lock the button group will turn into door lock control (value=7). For dimmers and motor controls the value changes into Multilevel Switch Control (value=1). All
other devices will turn the button group into Basic control (value=2). All configuration values can be changed if needed. When KFOB is primary controller the 

very

first device included

 will be 

automatically put into button group A

 and the command set will change according to the rules just mentioned. All other devices

need ot be put in button groups manually.

 

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs to be 

added to an existing wireless network

 to communicate with the

devices of this network. This process is called 

Inclusion

.

Devices can also be removed from a network. This process is called 

Exclusion

. Both processes are initiated by the primary controller of the Z-Wave network. This

controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is then performed doing a special manual action right on the device.

Inclusion

Please check the instructions in the quick start section how to include and exclude the device from a network.

Exclusion

Please check the instructions in the quick start section how to include and exclude the device from a network.

Product Usage

Depending on the button mode and operating modes configured using the configuration parameters the key fob can be used in different ways.

Button modes:

4 Groups are controlled with single button (parameter 1/2 = 0)

 The four buttons 1-4 control one single control group each: 1->A, 2->B, 3->C, 4->D. Single click

turns devices in the control group on, double click turns them off. Click and hold can be used for dimming.

2 Groups are controlled with two buttons (parameter 1/2 = 1)

 The buttons 1 and 3 control the control group A (button one turns on, button three turns off), the

buttons 2 and 4 control the control group B (button two turns on, button four turns off). In case dimmers are controlled, holding down the larger button will dim up,
holding down the smaller button will dim down the load. Releasing the button will stop the dimming function.

4 Groups are controlled with two buttons and double click (parameter 1/2 = 2)

 This mode enhances the previous mode and allows to control two further

control groups C and D using double clicks.

Summary of Contents for POPE009204

Page 1: ...evices will turn the button group into Basic control value 2 All con guration values can be changed if needed When KFOB is primary controller the very rst device included will be automatically put int...

Page 2: ...atch the position of the white rubber and make sure the silver buttons t exactly into the nipples of the rubber The device can be operated in two different modes the operation mode and the management...

Page 3: ...is process is called Exclusion Both processes are initiated by the primary controller of the Z Wave network This controller is turned into exclusion respective inclusion mode Inclusion and Exclusion i...

Page 4: ...irect Control of associated devices with On Off Dim commands and implements communication patterns 6 and 7 Please turn the button mode to separate to allow different a scene ID on every button Scene A...

Page 5: ...e called association groups and they are always related to certain events e g button pressed sensor triggers In case the event happens all devices stored in the respective association group will recei...

Page 6: ...allow con guring signed values In order to set values in the range 128 255 the value sent in the application shall be the desired value minus 256 For example To set a parameter to 200 it may be neede...

Page 7: ...all 4 Send scenes 5 Send precon gured scenes 6 Send precon gured scenes 7 Control door lock 8 Central scene to gateway Parameter 14 Command to control Group D This parameter de nes the command to be s...

Page 8: ...To same node as Wake Up Noti cation 2 Broadcast to neighbors Technical Data Dimensions 30x55x15 mm Weight 32 gr Hardware Platform ZM5202 EAN 0019962009204 IP Class IP 20 Battery Type 1 CR2032 Device T...

Page 9: ...national users community such as www z wave info and others If your question can t be answered there please use www popp eu support or contact us by email info popp eu While the information in this ma...

Reviews: