Section V: Operation
water temperature setting, this parameter, when set to NO, requires this unit to be displayed on the control panel before
changing any of the set points. The other screens for Pool Water Temperature Control, Staged Dehumidification, and
Stage 2 Offset are not available when this parameter is set to NO.
Changing Set Points
Each unit on the network maintains two groups of set points, network and local. If a unit has the Enable Network Control
parameter set to YES and the Water Temperature Control parameter set to NETWORK, it will control to the network
set points. Set points changed when the remote interface unit is displaying this unit will be changed in every unit on the
network with the same NETWORK and Water Temperature Control parameters. Units that are configured for Network
Control and LOCAL water temperature control will control using local water temperature set point, the network air
temperature and relative humidity set points. When the air temperature and relative humidity set points are changed
when the remote interface unit is displaying the unit, they will be changed in all units configured for Network control.
The water temperature set point will only be changed in the unit currently being displayed by the remote interface unit.
Units that are not configured for Network Control will use all local set points. Therefore any set points changed while the
remote interface unit is displaying this unit will only be changed in this unit.
ECC-PCP SERVICE
SERVICE MENU
To access the service menu:
•
Press the PRG key to access the main menu.
•
Use the arrow keys to scroll to the menu selection for Service and then press the Enter key.
• A password is required to access the service menu.
The following sub-menus are available in the service menu.
I/O CONFIGURATION
Digital Inputs
This menu contains a screen for each digital input. Each screen contains the following parameters:
• Status of the data point linked to the input.
• Status of the raw digital input.
• Input type.
The following parameter list shows the available digital input screens.
• Defrost Switch
• Cpr High Temp
•
Water Flow
•
Fire Trip
• AC Proof
• Cpr High Prs
•
Fan Overload
•
Low Pressure
• Purge Input
Digital Outputs
This menu contains a screen for each digital output. Each screen contains the following parameters:
• Current output status
•
Requested output status
•
Override