COMMISSIONING INSTRUCTION
The Zonemaster single VAV has two parameters, room temperature and
minimum ventilation, that should be set in the commissioning stage.
1. Initiating and Exit Setting Process
1)
Hold down both
and
buttons for
about 5 seconds until the LCD displays ‘Setting’
on the top line of the LCD screen.
2)
At the setting mode, pressing
button at
any time will return to the normal operation
mode.
2. Room Temperature Sensor
The touchpad has an onboard sensor for temperature control. The sensor
can be calibrated to provide more accurate temperature control as follows.
1)
Using an accurate probe to measure the
temperature of the area you want to calibrate
and record the value.
2)
At the setting mode, press
button until
the LCD displays the ‘Sensor’ screen.
3)
Press
or
button to adjust the
displayed value to the value recorded.
3. Minimum Ventilation
Customers may prefer minimum ventilation during the climate control. This
ventilation allows a minimum
airflow
into the zone that is switched on. The
amount of ventilation can be set from 0 to 30% open with a default of 0%.
1)
At the setting mode, press
button until
the LCD displays the ‘Min Vent’ screen.
2)
Press
or
button to adjust the
percent value of the minimum ventilation as
desired.
Page 5