ZONEMASTER ZONE SWITCH (TWO ZONE) DAMPER CONTROL SYSTEM 

-

 Operation & Installation Instructions

 6

Problem

Suggested Action

No response from the 

touchpad / The LED does 

not turn On/Off.

• 

Check the power supply is on.

• 

Check the fuse in the power 

supply is not blown.

Dampers have no  

response when turned on 

or off

• 

Check if the cable from the 

touchpad to the damper motor 

is plugged in properly.

• 

Check if the cable is faulty with 

a cable tester. If the cable tests 

as faulty replace the cable.

• 

Check if the damper motor 

is faulty by connecting the 

same zone output port to a 

spare damper motor. If the 

motor tests faulty, replace the 

damper motor.

Zones don’t open/close 

as desired

• 

Check if the damper motor 

of that particular zone is 

connected to the right port on 

the touchpad.

Damper Motor drives the 

wrong way

• 

Damper blade might be 

installed in the wrong 

position. If the blade position 

is incorrect, reposition the 

blade by removing the damper 

motor and then re-align to the 

respective position.

• 

Check if the cable connecting 

the damper motor and the 

touchpad is faulty. If the cable 

tests as faulty, replace the 

cable.

8) Troubleshooting Guide

Summary of Contents for Zonemaster Zone Switch

Page 1: ...ZONE SWITCH TWO ZONE DAMPER CONTROL SYSTEM Operation Installation Instructions www zonemaster com au www polyaire com au 2012 Polyaire Pty Ltd ...

Page 2: ......

Page 3: ... Exploded Diagram b Applying Zone names to Zones c Applying 2 zone label 7 Installing the Touchpad 8 Troubleshooting Guide APPENDIX A SPECIFICATIONS APPENDIX B ZONEMASTER CABLE TESTER 3 3 3 3 3 4 4 4 4 5 5 6 7 8 TABLE OF CONTENTS Liability Please read the instructions before installing this Zonemaster Zoning Control System Polyaire Pty Ltd does not accept any responsibility for loss or damage that...

Page 4: ...N The LED will light up indicating the zone is On Zone Opened The LED will stay on until the zone is turned OFF b Press the zone button again to turn the zone OFF The LED will turn OFF indicating the zone is OFF Zone Closed Note If power fails zones will automatically resume their original position prior to failure once power is returned OPERATION INSTRUCTIONS ZONE BUTTON LED ZONE NMAE LABEL ...

Page 5: ... zones Dampers are directly connected to the touchpad module LED indicators to show the ON OFF status of the zones Personalised zone labelling using stickers All zones automatically resume their original on off state once powered up after power outage 24 Volt for easy and safe installation and maintenance 3 Components 4 Wiring Schematic NOTE The zones on the touchpad are marked as Z1 and Z2 from t...

Page 6: ... Please make sure a separate dedicated open spill zone is designed with this system to prevent the above from occurring 6 Touchpad Preparation a Exploded Diagram Figure 1 shows an exploded view of the touchpad assembly b Applying Zone Names to Zones It is essential to apply correct names against the zones to make sure the end user is fully aware of the location of each zone The zone names are prin...

Page 7: ...overing film from the top of the label 7 Installing the Touchpad a Insert a flat head screw driver into the two gaps at the bottom of the casing and turn the screw driver blade just enough to open the cover as shown in Figure 3 then remove the back cover by sliding it out b Position the back cover on the wall about 1 5m high from the floor and mark the positions for screws and the cut out hole for...

Page 8: ...eplace the cable Check if the damper motor is faulty by connecting the same zone output port to a spare damper motor If the motor tests faulty replace the damper motor Zones don t open close as desired Check if the damper motor of that particular zone is connected to the right port on the touchpad Damper Motor drives the wrong way Damper blade might be installed in the wrong position If the blade ...

Page 9: ... Power 24W Components Power Consumption Touchpad 1VA Zone Output Output Voltage 24VAC 50 Hz Current 200mA 1 damper motor Environmental Requirements Operating temperature 0 O C to 60 O C Altitude 0 to 2000 meters Operating relative humidity 10 to 80 Avoid static electricity hazards Avoid electromagnetic radiation sources Avaoid dust contamination Avoid highly corosive environments Maximum Single Ca...

Page 10: ...before the start of the installation process thus reducing considerable diagnostic time if the fully installed system is subsequently found to have a problem 2 Features of the Cable Tester Tests Centre Latched and Left Latched RJ12 cables Portable quick and easy to test cables Bright LED s to indicate a faulty cable in the dark roof spaces 9V battery operated User Instructions provide Cable Tester...

Page 11: ...ZONEMASTER ZONE SWITCH TWO ZONE DAMPER CONTROL SYSTEM Operation Installation Instructions 9 ...

Page 12: ...POLYAIRE PTY LTD 11 13 WHITE ROAD GEPPS CROSS SOUTH AUSTRALIA 5094 TEL 08 8349 8466 FAX 08 8349 8446 www zonemaster com au www polyaire com au ...

Reviews: