background image

 

IK

E306

001GB

 

3

 

1

 

PURPOSE

 

The

 

DUR

4046

 

microprocessor

 

based

 

interactive

 

addressable

 

optical

 

smoke

 

detector

 

is

 

designed

 

for

 

detection

 

of

 

visible

 

smoke

 

that

 

is

 

concurrent

 

with

 

most

 

fire

 

combustion.

 

It

 

enables

 

a

 

fire

 

detection

 

at

 

a

 

start

 

of

 

its

 

flameless

 

stage

 

when

 

material

 

starts

 

to

 

smoulder,

 

and

 

therefore

 

generally,

 

a

 

long

 

time

 

prior

 

to

 

appearance

 

of

 

an

 

open

 

flame

 

and

 

a

 

noticeable

 

rise

 

in

 

temperature.

 

The

 

detector

 

is

 

characterised

 

by

 

a

 

high

 

resistance

 

against

 

wind,

 

pressure

 

change

 

and

 

steam

 

condensation.

 

It

 

is

 

very

 

sensitive

 

to

 

visible

 

smoke.

  

The

 

DUR

4046

 

addressable

 

optical

 

smoke

 

detectors

 

operate

 

only

 

in

 

the

 

POLON

 

4000

 

fire

 

detecting

 

and

 

alarm

 

system

 

control

 

panel

 

addressable

 

loop

shaped

 

lines.

   

The

 

detectors

 

are

 

equipped

 

in

 

internal

 

short

 

circuit

 

isolators.

 

2

 

TECHNICAL

 

SPECIFICATIONS

 

Operating

 

voltage

 

16.5

 

V

 

÷

 

24.6

 

V

 

Maximum

 

quiescent

 

current

 

draw

 

≤ 

150

 

µA

 

Maximum

 

installation

 

height

 

*)

 

12

 

m

  

Maximum

 

supervised

 

area

 

*)

 

60

 

÷

 

80

 

m

2

  

Operating

 

temperature

 

from

 ‐

25

 

°C

 

to

 

+55

 

°C

 

Allowable

 

relative

 

humidity

 

up

 

to

 

95

 

%

 

at

 

40

 

°C

 

Dimensions

 

(without

 

base)

 

Ø

 

115

 

mm

 

x

 

43

 

mm

 

Number

 

of

 

sensitivity

 

levels

 

3

 

Mass

 

(without

 

base)

 

0.2

 

kg

 

Standard

 

colour

 

white

 

Address

 

coding

 

method

 

programmable

 

at

 

the

 

control

 

panel

 

 

*)

 

see

 

design

 

guidelines

 

3

 

SAFETY

 

CONDITIONS

  

3.1

 

Repairs

 

and

 

maintenance

  

Any

 

maintenance

 

works

 

or

 

periodic

 

inspections

 

shall

 

be

 

executed

 

by

 

skilled

 

personnel

 

employed

 

by

 

companies

 

authorised

 

and

 

trained

 

by

 

POLON

ALFA.

  

Any

 

repairs

 

must

 

be

 

carried

 

out

 

by

 

the

 

manufacturer.

 

POLON

ALFA

 

bears

 

no

 

responsibility

 

for

 

the

 

operation

 

of

 

any

 

apparatus

 

being

 

repaired

 

by

 

unauthorised

 

personnel.

 

 

3.2

 

Works

 

at

 

height

  

Any

 

detector

 

installation

 

works

 

carried

 

out

 

at

 

height

 

must

 

be

 

executed

 

with

 

particular

 

care

 

utilising

 

tools

 

and

 

machinery

 

in

 

good

 

working

 

condition.

  

Special

 

attention

 

shall

 

be

 

given

 

to

 

stability

 

of

 

ladders,

 

elevators,

 

lifts,

 

etc.

 

Summary of Contents for DUR‐4046

Page 1: ...POLON 4000 INTERACTIVE FIRE DETECTION AND ALARM SYSTEM DUR 4046 ADDRESSABLE UNIVERSAL SMOKE OPTICAL DETECTOR Installation and Maintenance Manual IK E306 001GB IIIA Edition ...

Page 2: ...38 Polon Alfa Spółka z ograniczoną odpowiedzialnością Sp k 155 Glinki Street PL 85 861 Bydgoszcz POLAND 05 1438 CPD 0011 EN 54 7 DUR 4046 Smoke Detector utilising scattered light effect addressable multi state universal detachable Application fire safety Technical data IK E306 001GB manual Read the manual carefully before the detector assembling and commissioning Any nonconformity with the instruc...

Page 3: ...age 16 5 V 24 6 V Maximum quiescent current draw 150 µA Maximum installation height 12 m Maximum supervised area 60 80 m2 Operating temperature from 25 C to 55 C Allowable relative humidity up to 95 at 40 C Dimensions without base Ø 115 mm x 43 mm Number of sensitivity levels 3 Mass without base 0 2 kg Standard colour white Address coding method programmable at the control panel see design guideli...

Page 4: ...tor is installed in the G 40 base where detecting line cables are connected to Fig 1 DUR 4046 detector main elements 5 PRINCIPLE OF OPERATION The DUR 4046 is a Tyndall effect based optical smoke detector light ray scattering on smoke particles Its basic element is a detecting optical module consisting of an electroluminescence diode that transmits light radiation and a photodiode acting as a recei...

Page 5: ...shes of the diode The detector sensitivity level is adjustable Its sensitivity is settled from the control panel level choosing one of available sensitivity levels 1st operation mode normal sensitivity 2nd operation mode increased sensitivity 3rd operation mode decreased sensitivity The detector operation modes besides the control panel alarm variants entails that the user is able to adapt in the ...

Page 6: ...arm evoking in future Fig 2 Detector elements after dismantling The detector assembling and dismantling is shown on Fig 2 In order to dismantle the detector it is necessary to a pressing the net long tongue turn the cover right in the basket until it is taken out b remove two screws that fix the labyrinth and take the labyrinth out c perform the necessary cleaning ...

Page 7: ...re intended to operate in loops in loops with straight branches or in radial detection lines of the POLON 4000 system control panels see the POLON 4900 system control panel Installation and Maintenance Manual The detectors are installed in the 40 model range bases The detection line connection is presented in the G 40 base Installation and Maintenance Manual An additional optical alarm signal of a...

Page 8: ...8 IK E306 001GB Fig 3 Clamps of base interoperating with DUR 4046 plug IK E306 001GB 06 2011 01 2012 ...