background image

 

 

 

 

POLON

 

4000

 

INTERACTIVE

 

FIRE

 

DETECTION

 

AND

 

ALARM

 

SYSTEM

 

 

DUR

4046

 

ADDRESSABLE

 

UNIVERSAL

  

SMOKE

 

OPTICAL

 

DETECTOR

 

 

 

Installation

 

and

 

Maintenance

 

Manual

 

IK

E306

001GB

 

 

IIIA

 

Edition

 

Summary of Contents for DUR‐4046

Page 1: ...POLON 4000 INTERACTIVE FIRE DETECTION AND ALARM SYSTEM DUR 4046 ADDRESSABLE UNIVERSAL SMOKE OPTICAL DETECTOR Installation and Maintenance Manual IK E306 001GB IIIA Edition ...

Page 2: ...38 Polon Alfa Spółka z ograniczoną odpowiedzialnością Sp k 155 Glinki Street PL 85 861 Bydgoszcz POLAND 05 1438 CPD 0011 EN 54 7 DUR 4046 Smoke Detector utilising scattered light effect addressable multi state universal detachable Application fire safety Technical data IK E306 001GB manual Read the manual carefully before the detector assembling and commissioning Any nonconformity with the instruc...

Page 3: ...age 16 5 V 24 6 V Maximum quiescent current draw 150 µA Maximum installation height 12 m Maximum supervised area 60 80 m2 Operating temperature from 25 C to 55 C Allowable relative humidity up to 95 at 40 C Dimensions without base Ø 115 mm x 43 mm Number of sensitivity levels 3 Mass without base 0 2 kg Standard colour white Address coding method programmable at the control panel see design guideli...

Page 4: ...tor is installed in the G 40 base where detecting line cables are connected to Fig 1 DUR 4046 detector main elements 5 PRINCIPLE OF OPERATION The DUR 4046 is a Tyndall effect based optical smoke detector light ray scattering on smoke particles Its basic element is a detecting optical module consisting of an electroluminescence diode that transmits light radiation and a photodiode acting as a recei...

Page 5: ...shes of the diode The detector sensitivity level is adjustable Its sensitivity is settled from the control panel level choosing one of available sensitivity levels 1st operation mode normal sensitivity 2nd operation mode increased sensitivity 3rd operation mode decreased sensitivity The detector operation modes besides the control panel alarm variants entails that the user is able to adapt in the ...

Page 6: ...arm evoking in future Fig 2 Detector elements after dismantling The detector assembling and dismantling is shown on Fig 2 In order to dismantle the detector it is necessary to a pressing the net long tongue turn the cover right in the basket until it is taken out b remove two screws that fix the labyrinth and take the labyrinth out c perform the necessary cleaning ...

Page 7: ...re intended to operate in loops in loops with straight branches or in radial detection lines of the POLON 4000 system control panels see the POLON 4900 system control panel Installation and Maintenance Manual The detectors are installed in the 40 model range bases The detection line connection is presented in the G 40 base Installation and Maintenance Manual An additional optical alarm signal of a...

Page 8: ...8 IK E306 001GB Fig 3 Clamps of base interoperating with DUR 4046 plug IK E306 001GB 06 2011 01 2012 ...