  check the equipment for any possible vibration 

  check the installation protection and tightness of the plumbing / hoses 

 
 

9. Maintenance 

 

In normal use the WHT heaters are almost maintenance free except for the air intake filter. 
To assure trouble-free working of the equipment the heaters must be checked regularly and 
cleaned if necessary. 
 

Air intake filter should be cleaned regularly and changed into new one when 
necessary. Do not use the equipment without the filter! 
 

Before maintenance: 

  close the water circulation and prevent it from opening 

  wait until the heat exchanger has cooled down 

  stop the heater appropriately remove it from the electric network 

 

Cleansing agents 
 

Do not use any abrasive scratchy or agents including solvents. Soft cloth and soap solution 
are enough in most cases to remove the dirt. 
 

Cleaning the equipment: 
 

  remove the filter unit and clean or replace it with a new one 

  clean the air intake openings and discharge baffles 

  clean the fan blade with e.g. compressed air, mild pressure. 

NOTE! Do not lose the 

balancing weights of the fan blade!

 

  heat exchanger baffles are cleaned by blowing, vacuum-cleaning or soft brush. The 

most dirt from the fan blades and baffles can be removed by soap solution 

  in case the fan motor holders and guard net have been removed they should be 

reinstalled after which the free rotation of the fan blade should be checked carefully 

 

Maintenance precautionary measures: 
 

  do not water the motor 

  in any case do not use high pressure water or steam 

  avoid damaging or bending the baffles and fan blades during maintenance and make 

sure not to remove the balancing weights of the fan blade 

 

Maintenance repair: 
 

  Always before repair unplug the equipment from electric network to prevent the 

heater from turning on 

  In cold conditions empty the heat exchanger from water or fill it with e.g. glycol 

Note! Emptying the heat exchanger can only be done with compressed air. 

 

RAMIRENT

Summary of Contents for POLAR WHT 45

Page 1: ...USER MANUAL 1 06 POLAR WHT 45 Portable fan heater for water carried central heating R A M I R E N T ...

Page 2: ...sten direktiivien ja standardien vaatimuksia Type of equipment Laitetyyppi Water to air heater Kiertovesitoiminen lämpöpuhallin Type of designation Tyyppimerkintä POLAR WHT 45 Directives Direktiivit Machinery Directive Konedirektiivi 89 396 EEC Low Voltage Directive Pienjännitedirektiivi 73 23 EEC EMC directive EMC direktiivi 89 336 EU Manufacturer Valmistaja POLARTHERM OY Polarintie 1 FIN 29100 L...

Page 3: ...f the equipment water couplings and electricity is allowed only by trained professional personnel the equipment should not be placed or used in highly combustible or explosive environment the equipment should be placed outside passages min 1 m safety area around the heater water hoses should be placed and protected to prevent them from being damaged when moving equipment while connected to water c...

Page 4: ... coupling consists of 1 aluminium cam lock joints with female joint for incoming water and male joint for return water incoming water is below left elbow joint reducing double nipple and male cam lock joint on the incoming side return water is above right elbow joint with air valve reducing double nipple closing valve and female cam lock joint made to order joints etc removed and circulated water ...

Page 5: ... where the cell is frozen 7 Electric connection Neglecting proper user manuals and electrical diagrams or changing them may cause malfunctions and other consequences In these cases the warranty is void Connecting the equipment The heater is connected to electric power supply 400 230 V 3N 50Hz 16 A using a 16 A electric plug Plug is equipped with a phase turning switch to enable turning the rotatio...

Page 6: ...lean or replace it with a new one clean the air intake openings and discharge baffles clean the fan blade with e g compressed air mild pressure NOTE Do not lose the balancing weights of the fan blade heat exchanger baffles are cleaned by blowing vacuum cleaning or soft brush The most dirt from the fan blades and baffles can be removed by soap solution in case the fan motor holders and guard net ha...

Page 7: ...15 air outlet rubber nozzles Ø125 95 pcs 4 sound absorber yes noise level dB A 70 protection class IP 34 circulated water couplings standard 1 cam lock circulated water couplings R11 4 external thread heating intermediate agent hot water max 130 C water pressure max bar 16 nominal circulated water flow nominal heat output m3 h 1 9 0 54 l s water cell counter pressure nominal water flow kPa 4 8 48 ...

Page 8: ...4 6 30 15 46 1 25 10 42 6 27 5 48 8 28 70 50 0 34 9 30 5 31 4 34 10 27 6 36 15 22 8 36 20 18 2 37 15 52 9 31 10 49 7 33 5 46 1 35 80 60 0 42 6 37 5 38 8 41 10 34 9 43 15 31 4 44 20 27 6 46 15 54 0 31 10 50 8 34 5 48 1 36 90 70 0 45 1 39 5 41 9 44 10 38 6 46 15 35 3 48 20 31 8 50 110 90 0 58 8 54 R A M I R E N T ...

Page 9: ...racting R11 4 1 2 pcs 65355 12 Double nipple R1 2 pcs 65400 13 Valve R1 thermostat regulator with fixed temp sensor 67600 67700 14 Air screw 67150 15 Vent valve automatic 67550 16 Branch tee 65500 17 Contracting nipple R1 2 3 8 65600 18 Cam lever joint R1 male female aluminium 82450 19 Cover plugs for cam lever joints 82451 20 Sound absorber 69210 21 4 way air outlet adapter 22 Air outlet corner p...

Page 10: ...10 A F1 3 F5 6 A 1 5 mm 1 5 mm X1 6 X1 1 2 X1 X1 3 X1 9 X2 1 S3 C 2 M Fan motor WHT 45 K1 Contactor Danfoss CI9 230 V S1 Main switch 0 1 S3 Low twmp thermostat 4 C Imit 20211 F1 3 Fuses 10 A F4 Thermal relay motor Danfoss 4 6 2 A F5 Control fuse 6 A H1 Indicator Fan failure Arcolectric 230 V red P1 Hour counter 230 V X1 Terminal block 4 mm Wieland WK4 X2 Ground terminal X3 Appliance receptacle 3P ...

Reviews: