Polaris PGC 34-100-2NV Installation Instructions And Use & Care Manual Download Page 13

13

CONCENTRIC VENT TERMINATIONS

For new installations, install 2” Concentric vent kit model 

KGAVT0501CVT, part number 6910542.  See Manufacturer’s 

instructions for complete installation or call customer service at 

1-800-456-9805 for assistance or go to www.americanwaterheater.com.  
For planning purposes, see figures 10-13 below for vent terminal 

specifications.

Note:

  For replacement installations, previously installed 

American Water Heater Company supplied concentric vent kits 

are acceptable for use on 100,000-130,000 BTU/Hr models only. 

Make sure that the existing vent complies with current codes.

(14.6cm)

(15.7cm)

(8.9cm Dia.)

(42.2cm)

(84.77cm)

(4.8cm)

(3.8cm)

Figure 10: 2 Inch Concentric Vent

(2.54cm)

Figure 11: Through the Wall Termination

12” (30.5cm) Minimum 
clearance above 
anticipated snow level.  
24” (61cm) Max.

Figure 12: Through the Roof Termination

Notes:
1.  Support Horizontal Pipe Every 

Four Feet (1.2 m).  Support 

Vertical Pipe Every Six ft. (1.8 m).

4.  Increase The 12 Inch (30.5 cm) 

Minimum Above Grade To Keep 

Inlet Opening Above Anticipated 

Snow Levels.

5.  Slope All Piping Down Toward 

the Water Heater as follows: 

 ‡ ´3LSLQJVORSH

 ´3HU)RRWPPSHUPHWHU

 ‡ ´3LSLQJVORSH

 ´3HU)RRWPPSHUPHWHU

 ´FPPD[LPXPZKHQXVLQJ

´SLSH

*

*

*

18” 

(45.7cm) 

Max.

12” (30.5cm) 

Minimum Above 

Grade or 

Anticipated 

Snow Level.  

(See Note 2.)

See Note 4

Figure 13: Through the Wall Termination

For clarity, T&P discharge line not shown.  See the 

Temperature 

and Pressure Relief Valve

 section for requirements.

Concentric Venting Multiple Water 
Heaters (All Models)

When using two Polaris

®

 units, install vent terminations 

using either Method E or Method F below:

Note:

  For installation of more than two Polaris

®

 units,    

follow the pattern established in Method G.

2” (5.08 cm)

Max.

36” (.9144 m) Min.

2” (5.08 cm)

Max.

36” (.9144 m) Min.

Figure 13E, 13F, 13G

Summary of Contents for PGC 34-100-2NV

Page 1: ...s telephone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or...

Page 2: ...r these conditions we recommend the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance which is connected to the hot water system If hydrogen is p...

Page 3: ...orized service person The manufacturer and seller of this water heater will not be liable for any damages injuries or deaths caused by failure to comply with the installation and operating instruction...

Page 4: ...tally vented gas fueled heat ing appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The s...

Page 5: ...intain proper clearances as specified on the data plate Figure 1 Garage Installation Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance S...

Page 6: ...tolerance 1 9 cm 0 31 cm tolerance Note The trap should be aligned so that the exhaust pipe is in a vertical position close to the surface of the water heater Figure 2 Minimum Clearance Locations Back...

Page 7: ...ate line into the metal drain pan VENT PIPE SYSTEM Carbon Monoxide Hazard Follow all instructions to locate and install the vent pipe system Instructions can be found in this manual in state or local...

Page 8: ...shell housing by turning clockwise approximately 1 2 30 5 cm and pulling off of the internal clamshell housing see figure 4C Using your fingers or a small flat blade screwdriver remove the filter medi...

Page 9: ...vent pipe All joints in the inlet and outlet piping must be properly cemented Size and cut all piping before cementing 1 Cut the pipe end square and remove all ragged edges and burrs Make sure the in...

Page 10: ...12 in 30 cm min vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 ft 61 cm from the center line of the terminal E 12 in 30 cm min clearance to unven...

Page 11: ...Units on Page 12 for correct terminations if installing more than one Polaris gas water heater Alternative Horizontal Termination The combustion air and exhaust terminations may be raised up to 24 inc...

Page 12: ...ne or anticipated snow levels See figure 9 below Note See Venting Additional Polaris Units below if installing more than one Polaris gas water heater Venting Additional Polaris Units When using two 2...

Page 13: ...level 24 61cm Max Figure 12 Through the Roof Termination Notes 1 Support Horizontal Pipe Every Four Feet 1 2 m Support Vertical Pipe Every Six ft 1 8 m 4 Increase The 12 Inch 30 5 cm MinimumAbove Gra...

Page 14: ...supply use 1 NPT to the fitting marked HOT OUTLET 2 Always use a suitable grade of joint compound and be certain that all fittings are tightened properly 3 The installation of unions in both the hot...

Page 15: ...ill contaminate the potable water supply Closed System Thermal Expansion As water is heated it expands thermal expansion In a closed system the volume of water will increase As the volume of water inc...

Page 16: ...the water heater should be ver tical past any mixing valve or supply line to the heating system to remove air bubbles from the system Do not connect the water heater to any system or components previo...

Page 17: ...ine Must not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line Must not be capped blocked plugged or contain any valve between the relief...

Page 18: ...9 for gas piping installation 1 Install a readily accessible manual shut off valve in the gas supply line as recommended by the local utility Know the location of this valve and how to turn off the ga...

Page 19: ...onally listed recognized fuel gas and carbon monoxide CO detectors are recommended in all applications and should be installed using the manufacturer s instructions and local codes rules or regulation...

Page 20: ...electrical wiring to the water heater 1 Shut off the power at the electrical service box 2 Loosen the screws securing the access panel to the electrical compartment The electrical wiring diagram model...

Page 21: ...T L1 NEUTRAL GND PSI PSO PRESSURE SWITCH BLACK WHITE WHITE RED LED YELLOW LED GREEN LED BROWN YELLOW RED THERMOSTAT DIAL ORANGE GAS VALVE BROWN BLUE BLUE WHITE IGNITER RED GREEN YELLOW ORANGE RED 24V...

Page 22: ...1 8 per foot 10 5 mm per meter Away from corners other vents windows etc Alternate Horizontal Correct relationship outlet to inlet 12 Min 30 5 cm above anticipated snow level 2 exhaust outlet air inle...

Page 23: ...ich signals the beginning of the ignition sequence see figure 21 and Red Ignition control is signaling the gas valve to open Figure 21 Sequence of Operation When the thermostat calls for heat the blow...

Page 24: ...e thermostat is adjusted to its lowest temperature setting when it is shipped from the factory Water temperature can be regulated by moving the temperature dial to the preferred setting The preferred...

Page 25: ...eing shut down during freezing temperatures To drain the tank perform the following steps 1 Turn off the gas supply at the Manual Gas Shut off Valve Turn off the electrical supply to the water heater...

Page 26: ...Remove the gas valve from the unit keeping the rubber gasket with the gas valve 8 Remove the flange from the gas inlet side of the valve by removing the four 4 attachment screws Figure 25 Replacing t...

Page 27: ...arity Detection SC SL Soft Lockout Control Automatically resets after 60 minutes SL3 Soft Lockout Hard Lockout Control automatically resets after 60 minutes with a maximum of 3 resets followed by hard...

Page 28: ...28 SOFTWARE OPERATION SEQUENCE IGNITION CONTROL MODULE SOFTWARE OPERATION SEQUENCE...

Page 29: ...TE TRAP ASSEMBLY 32 COLD WATER TUBE ASSEMBLY 33 TEMPERATURE AND PRESSURE RELIEF VALVE 34 DRAIN VALVE 35 POTENTIOMETER 36 VENTURI GASKET not pictured 37 BLOWER ISOLATION RELAY TOOLS REQUIRED FOR SERVIC...

Page 30: ...3 4 40 1 2 41 6 3 8 5 1 2 6 5 8 150 PGC 34 150 2NV OR 2PV 34 150 2 OR 3 48 1 2 22 15 3 4 40 1 2 41 6 3 8 5 1 2 6 5 8 150 PGC 50 130 2NV OR 2PV 50 130 2 OR 3 62 3 8 22 15 3 4 54 1 2 55 6 3 8 5 1 2 6 5...

Page 31: ...31 NOTES...

Page 32: ...ed To obtain technical warranty or service assistance during or after the installation of this water heater visit our website at http www americanwaterheater com or call toll free 1 800 456 9805 P O B...

Reviews: