Polaris 9300 Diagnostic Instructions Download Page 3

4. 

If the pump and drive motors drive, the control unit 
has passed the test successfully.  Turn off the power 
to the control unit. 

NOTE

   The control unit is programmed to shut down 

power to the cleaner head within ten (10) sec-
onds in order to protect the motor from damage. 

C.  Diagnosing a Defective Motor Block or 

Floating Cable

1. 

Open the cleaner top and remove the 

fi

 lter canister. 

Unthread the screw securing the prop guard in place 
and remove the propeller guard (see Figure 6).

Figure 6.  Remove the Propeller Guard

Figure 8.  Remove the Propeller Guard

Figure 9.  Remove the Floating Cable

Figure 7.  Remove the Propeller and Flow Director

2. 

Remove the propeller and the 

fl

 ow director 

(see Figure 7).

3. 

Close the cover and turn the cleaner over so that it’s 
resting on its top.

4. 

Remove the four (4) screws from the bottom of the 
cleaner.  Remove the bottom plate/motor block 
(see Figure 8).

5. Disconnect 

the 

fl

 oating power cable from the motor 

block by removing the two screws connecting the 
cable to the block, then pulling the plug away from 
the block (see Figure 9). 

Page 3

Summary of Contents for 9300

Page 1: ... GFCI Such a GFCI receptacle should be provided by a qualified installer and should be tested on a routine basis To test the GFCI push the test button The GFCI should interrupt power Push the reset button Power should be restored If the GFCI fails to operate in this manner the GFCI is defective If the GFCI interrupts power to the pump without the test button being pushed a ground current is flowin...

Page 2: ...ting Cable to Test Box Figure 4 Checking for Air Flow Figure 3 Select the Cleaner Model Figure 5 Testing the Control Unit 4 Determine the corresponding button for the model being diagnosed 9300 or 9300xi Press the button to start the test see Figure 3 2 The drive cycle will turn on and will last for approximately five 5 seconds 3 The cleaner will then drive forward for approximately five 5 seconds...

Page 3: ...ace and remove the propeller guard see Figure 6 Figure 6 Remove the Propeller Guard Figure 8 Remove the Propeller Guard Figure 9 Remove the Floating Cable Figure 7 Remove the Propeller and Flow Director 2 Remove the propeller and the flow director see Figure 7 3 Close the cover and turn the cleaner over so that it s resting on its top 4 Remove the four 4 screws from the bottom of the cleaner Remov...

Page 4: ...lashing red lights on the diagnostic panel then the motor block is defective Replace the motor block and return old motor to Zodiac 6 Using the short test cable connect the motor block to the Polaris Quick Diagnostic Test Box see Figure 10 7 Once secured start the diagnostic test see Figure 11 All trademarks referenced herein are the property of their respective owners ZODIAC is a registered trade...

Reviews: