These settings refer  to the mode of operation of the  system and must be
made on initial start-up. Press  

- / +

 together  for  at  least  one  second.

the message 

C.O.S.t.

    will be displayed.

Press than repeatly

 MAX VENT 

until interested variable's message is

displayed  (see table below) : variable value and related message will be
displayed. Press

 + 

or

 -

 to set a new value and then 

MAX VENT

 to confirm.

The next system constant will then appear. You can press 

MAX VENT 

for a least two second

to escape and return to the 

Run Mode

.

COSt PROGRAMMING (System constants)

"HAND MODE"

In some start-up conditions may be useful to work in "hand" mode.
Power off theprocessor, press

 +

 key and keep it pressed giving power on:

 HAnd

  message will be displayed (release now  

 key).

Push 

 + 

 until is displayed number required to be handed (see table relays

"

N° Relay

") and push 

MAX VENT

 for activing relay.

Pushing again 

 + 

 for increase relay number previous relay is disactivated. You can

press 

MAX VENT

 for a least  two seconds to escape and return to the 

Run Mode.

STATUS INDICATION LAMPS

VEL 4 ON

ProP

1/3 ProP

1/3 ProP

1/3 ProP

HEAT

VEL. 1 OFF

r.HEA

HEAT ON

vEnt

°C VENT

key setting

0.2°

0.2°

0.2°

0.2°

M i n i m u m
V e n t i l a t i o n
conditioned

Step from 

0

 to 

1

 become

according to chosed 

COSt

option 

tYPE 1-2-3-4

.

d.HEA

TEMP.AMB.

HEAT ON

V1

V2

V3

V4

M a x i m u m
Ventilation
conditioned

OPERATING DIAGRAM

The lights situated at the bottom of the  display  show the state of the various relays as set out below.

Speed 3 Selected

Speed 4 Selected

Speed 2 Selected

Speed 1 Selected

Speed 0 Selected

Heating On

Lamp.

N° Relay

HEAT

0

1

2

3

4

HEAT

1

0

0

0

0

0

5

VENT 1

0

0

1

0

0

0

1

VENT 2

0

0

0

1

0

0

2

VENT 3

0

0

0

0

1

0

3

VENT 4

0

0

0

0

0

1

4

Output relay

Table of relay Outputs with tYPE1-2-3-4-9  (Variable speed control)

Lamp.

N° Relay

HEAT

0

1

2

3

4

HEAT

1

0

0

0

0

0

5

VENT 1

0

0

1

0

0

0

1

VENT 2

0

0

1

1

0

0

2

VENT 3

0

0

1

1

1

0

3

VENT 4

0

0

1

1

1

1

4

Output relays with tYPE 14  (see COSt)

Table of relay Outputs with tYPE 14 (On-Off regulation type)

Mess. Value

Meaning

Note

ProP

3.0°

 ° Ventilation proportional band

*1)

r.HEA

-0.5°

 ° HEAT setting referring to °C VENT

*2)

d.HEA

0.2°

 ° HEAT differential

*2)

tEnP

=1

 Temperature representation

*3)

Ad.tE

 0.0°

 ° input sensor temperature correction

*4)

tYPE

=1

 Start ventilation actioning mode

*5)

*1)

 From lower value ventilators starts at speed n°1 at temperature setted on

°C  VENT 

key

 

and reach speed n°4 at temperature

 °C VENT + ProP

.

*2)

 This set is a relative set reffered to temperature setted on

°C VENT

 key.

For example if is setted

 °C VENT=25.0°

 and

 r.HEA=-0.5°

 heating command

(HEAT) will start at 24.5° (25.0°-0.5°).
Heating will be OFF after 0.2° (value 

d.HEA

).

*3) tEnP =0

 :  

°C  

Temperature range.

tEnP =1 

 °F  

Temperature range.

*4) 

You can correct the readings on the sensor (

or

 -

).

*5)

 Different mode of ventilator initial start-up optionally settable (step from

 0 

to 

1

speed).

tYPE= 1

  : 0 to 1 step become in normal mode.

tYPE= 2 

 : 0 to 1 step become with a momentary

 10

  seconds at speed

 2

.

tYPE= 3 

 :  0 to 1 step become with a momentary 

  5  

seconds at speed

 3

.

tYPE= 4 

 :  0 to 1 step become with a momentary 

  5  

seconds at speed

 4

.

tYPE=13  

: Heating mode ventilation.

tYPE=14  

: Progressive speed (On-Off regulation type).

Options  2, 3 , 4  permits to make an easy opening of shutter models ventilators.
Option 13 permits Heater mode ventilation (low temperature = hight speed; in
other options high temperature= high speed).
Option 14 permits On-Off regulation speed (in other condition regulation is for
variable speed control).

With

 tYPE = 13 :

V0       V4
V1       V3
V2       V2
V3       V1
V3       V0

Heater mode ventilation