Pneumercator MODBUS RTU RS-485 Instruction Manual Download Page 6

 

MODBUS RTU Instruction Manual - 2017-11-02.docx 

Page 6 of 14 

November 2, 2017 

 
1.3.2 Line Termination Resistor 

 

The RS-485 bus requires that the end-of-run device be terminated with a 120-ohm resistor. This is 
accomplished by setting the LINE TERMINATION switch to “ON” if the MODBUS Interface Card is 
the last device on the bus. Otherwise this switch should be set to “OFF”. 
 

 

 
1.4 LED Indicators 

 
Visual  indication  of  Modbus  activity  is  provided  by  a  SLAVE  RECEIVE  (RX)  and  a  SLAVE 
TRANSMIT (TX) LED. Note that SLAVE RECEIVE indicates for all MASTER/HOST transmissions. 

DWG NO. 20197 REV. B

I

N

O
U

T

MODBUS CARD

(TOP VIEW)

"OFF" POSITION
TO ADD ANOTHER
TMS/LC2000

WHT/BL (A+)

BL/WHT (B-)

SHIELD (SHD)

WHT/BL (A+)

BL/WHT (B-)

SHIELD (SHD)

2 CONDUCTOR SHIELDED

RS-485 COMM. CABLE

I

N

O
U

T

MODBUS CARD

(TOP VIEW)

WHT/BL (A+)

BL/WHT (B-)

SHIELD (SHD)

"ON" POSITION
FOR LAST
TMS/LC2000

END-OF-RUN

TX

RX

SHD

B-

A+

SH

D

B-

A

+

OFF

TERM

ON

TX

RX

SHD

B-

A+

SH

D

B-

A

+

OFF

TERM

ON

SHIELD WIRE SHOULD

BE CUT BACK AND LEFT

UNTERMINATED

THIS END ONLY

MODBUS MASTER

(EXAMPLES: BAS, BMS, PLC)

TERMINAL BLOCK

(SHOWN FOR REF.)

WHT/BL (A+)

BL/WHT (B-)

SHIELD (SHD)

SHIELD WIRE SHOULD

BE CUT BACK AND LEFT

UNTERMINATED

THIS END ONLY

Summary of Contents for MODBUS RTU RS-485

Page 1: ...TMS LC2000 console to a host or master computer system supporting MODBUS RTU protocol Communications is over a half duplex single twisted pair RS 485 cable Information available from the TMS LC2000 in...

Page 2: ...nsole 1 0 Installation and Setup Installation and setup of the 900552 Modbus RTU Interface Card requires no programming on the TMS LC2000 console Simply select the desired slave address and baud rate...

Page 3: ...es Slave SW 6 SW 5 SW 4 SW 3 SW 2 SW 1 Device Address Address MSB Address 5SB Address 4SB Address 3SB Address 2SB Address LSB 1 CLOSED CLOSED CLOSED CLOSED CLOSED CLOSED 2 CLOSED CLOSED CLOSED CLOSED...

Page 4: ...EM ENCLOSURE PARTIALLY SHOWN ON OFF SWITCH SEE WARNING MAIN BOARD PROCESSOR CARD DWG NO 20200 REV N C MAIN BOARD STANDOFF MODBUS CARD ON OFF SWITCH SEE WARNING SYSTEM ENCLOSURE PARTIALLY SHOWN DWG NO...

Page 5: ...ations having a nominal impedance of 120 ohms Maximum cable distance supported is 4000 as per below drawing See 3 0 Product Specifications for example part numbers DWG NO 20196 REV A END OF RUN TMS LC...

Page 6: ...RANSMIT TX LED Note that SLAVE RECEIVE indicates for all MASTER HOST transmissions DWG NO 20197 REV B I N O U T MODBUS CARD TOP VIEW OFF POSITION TO ADD ANOTHER TMS LC2000 WHT BL A BL WHT B SHIELD SHD...

Page 7: ...ster to Slave TMS LC2000 Query Read TMS LC2000 Data Slave TMS LC2000 to Master Response Read TMS LC2000 Data FC SLA STA 5 6 7 8 1 2 3 4 NPR EC Error Check 16 bit CRC Number of Points to Read Start Add...

Page 8: ...f for any reason communications between these two processors is lost the MODBUS processor will set the LSB of the MSR to 1 Additionally the MODBUS processor will force all tank data to full positive s...

Page 9: ...0 1 C Water Height High Water Height Low 12 13 S 31 Bits 0 1in 1mm Ullage High Ullage Low 14 15 32 Bits 1 GL 1 LT Ullage is based on 85 90 95 or 100 of tank capacity depending on TMS configuration set...

Page 10: ...Theft Alarm DB11 Water Setpoint Alarm HIGH DB12 Product Setpoint Alarm 3 LOW DB13 Product Setpoint Alarm 2 HIGH DB14 Product Setpoint Alarm 1 HIGH HIGH DB15 In Tank Leak Alarm MSB N A DB16 N A WiS Err...

Page 11: ...nk Leak Alarm N A DB16 N A WiS Error DB17 N A WiDAM Timeout Error DB18 N A WiDAM Low Battery Warning DB19 N A Probe Temperature Error DB20 spare DB21 Product Setpoint Alarm CRIT LOW DB22 Product Setpo...

Page 12: ...17 40199 24 23 22 21 40200 28 27 26 25 40201 32 31 30 29 40202 36 35 34 33 40203 Sensor 40 39 38 37 2 1 3 1 Sensor Data Register Status Detail Status MSB 3SB 2SB LSB Normal 0 0 0 0 Alarm 0 0 0 1 Faul...

Page 13: ...etail Register DB15 12 DB11 8 DB7 4 DB3 0 40204 4 3 2 1 40205 8 7 6 5 40206 12 11 10 9 40207 16 15 14 13 2 1 4 1 Contact Closure Data Register Status Detail Status MSB 3SB 2SB LSB Not Active 0 0 0 0 A...

Page 14: ...ded RS 485 Cable Belden 9841 PVC Jacket 89841 FEP Teflon Jacket or similar Maximum Cable Length 4000 Feet 1200 Meters total to end of run LED Indicators TX Slave Transmit RX Global Receive Serial Data...

Reviews: