Control input
Configurable as a direct or inverse switch or key!
Functions:
Locking front operating,
resetting of latched alarms, slave pointers,
integrator;
activating tare-, sample&hold function;
switchover between inputs
Counter input (optional)
Pulse counter for up or down counting, non storing
Active edge:
configurable
Width of counter register:
31 bits
Display range:
Configurable via counter divisor,
8-digits
can be repartitioned to 2 lines
Counter divisor:
adjustable 0.1...9999
Start value:
adjustable
End value:
adjustable; reaching can be
signalled via output
Counter evaluation:
At intervals of 100 ms
(140 ms with INP2 measurement)
Reset:
Via key combination,
Limit value
Counter input with option contact
Count frequency, max.:
5 Hz with square wave 1:1
pulse duration, min.:
100ms
Counter input with option optocoupler
Count frequency, max.:
100 kHz
with square wave 1:1
Pulse duration, min.:
5µs
Effects to active transmitters connected to INP1, INP2 can occur.
Frequency input (optional)
Input with option optocoupler
Frequency range:
0...100 kHz with square wave 1:1
Gate time:
adjustable, 0.1... 20s
Process value:
scalable
Effects to active transmitters
connected to INP1, INP2 can
occur.
OUTPUTS
RELAY OUTPUTS OUT1, OUT2
Contact type:
2 normally open contacts with
common connection
Maximum contact rating:
500 VA, max. 250 V, max. 2A at
48...62 Hz, resistive load
Minimum contact rating:
6V, 1 mA DC
Number of electrical
switching cycles:
for I= 1A/2A:
?
800.000 / 500.000
(at ~ 250V (resistive load))
Note:
If the relays OUT1 and OUT2 operate external contactors, these
must be fitted with RC snubber circuits to manufacturer
specifications to prevent excessive voltage peaks at switch-off.
OUT3 AS UNIVERSAL OUTPUT
Galvanically isolated from the inputs. Parallel current/voltage
output with common ‘minus’ terminal (combined use only in
galvanically isolated circuits).
Freely scalable
Resolution:
14 bits
Dynamic response (step change
of input signal) T90:
Output follows the input
ß
540 ms
Tracking error I/U:
ß
2%
Residual ripple:
ß_
1%
(rel. to range end)
0...130 kHz
Current output
0/4...20 mA, configurable.
short circuit proof
Linear range:
-0.5...23 mA
Load:
ß
700
[
Load effect:
ß
0,02%
Resolution:
ß
1,5 µA
Error:
ß
0.1%
Voltage output
0/2...10V, configurable
not continous short-circuit proof
Linear range:
-0,15...11,5 V
Load:
?
2 k
[
Load effect:
ß
0.06%
Resolution:
ß
0.75 mV
Error:
ß
0.1%
Additional error when using
ß
+0.09%
simultaneously the current
output:
OUT3 as transmitter supply
Output:
22 mA /
?
13 V DC
OUT3 as logic signal
Load
ß
700
[
0/
ß
23 mA
Load > 500
[
0/> 13 V