S MA RT SC AN
®
In the narrow kitchen (below) a wall mounted unit is used to protect the space with a 2 spray configuration.
The manifold is set up with 2 x A16 nozzles and 2 blanks.
C) Installing the Automist Head
IMPORTANT:
When installing an Automist head with four nozzles you must make sure the active nozzles
are pointing into the room and not towards the wall. PTFE tape should be wrapped approximately three
times around the hosetail thread that enters the spray head.
Assemble the spray head. In the correct orientation the screw is positioned alongside the union.
There will be interference between the male/male union and the head fixing screws. This is expected and
helps to seal the union thread with PTFE to avoid leaks.
Cut a hole in the appropriate location of the mounting box for the high pressure hose. An elbow
connection is included in the kit for use when necessary.
Spray head
Washer
M5 screw
Hose tail
PTFE tape