INSTALLATION MANUAL 

 

 

Name: 

Pressure recorder

 

Type: 

MacR6

 

Variant: 

Z0 & Z0-P

 

Communication protocol: 

GAZMODEM2

   

 
 

 

 
 
 
 
 

1.  PREPARING THE DEVICE 

 

 

Remove  six  TORX  T10  screws  from  back  of  the 
cover. 

 

Next place the Micro SIM card into the holder as 
shown in the picture. There is no need to remove 
the battery to insert the SIM card. 

 

In  the  next  step  put  the  device  together  and 
tighten 

the 

screws 

with 

0,65-0,75Nm 

momentum.

 

 
 
 

 

SIM card and antenna assembly is allowed only out of the hazardous explosive 
zone.  

 
 

 

Delivered devices may have the display turned off. To wake it up close the magnet (i.e. OptoBTEx 
head to the OPTICAL INTERFACE window. SLEEP 3 sign will appear. Repeat closing magnet until 
START sign will appear. Procedure presented in the tutorial movie => 

red QR code. 

 

 
 
 
 
 
 
 
 
 
 
 

RELATED TO FIRMWARE: 

 

 

 

PROGRAM SERIE: MacR6-P S001.04 

 

 

Document version: 1.1 
January-2019

 

 

 

 

 

 

 

 

Summary of Contents for MacR6

Page 1: ...s no need to remove the battery to insert the SIM card In the next step put the device together and tighten the screws with 0 65 0 75Nm momentum SIM card and antenna assembly is allowed only out of th...

Page 2: ...pheres are prescribed in Directive 1999 92 EC of the European Parliament and of the Council of 16 December 1999 ATEX 137 Worker Protection Directive Installation environment must guarantee the strong...

Page 3: ...ressure sensor assembly it is recommended to perform SEr 8 menu to begin pressure measurement test measurement every 5 seconds for one minute Value of pressure will be shown on LCD 4 CONNECTION WITH S...

Page 4: ...y destination number without YYYYYYYYYYY phone number o data server address way of typing address port i e www ewebtel com 80 o time synchronization option winter summer auto change Choosing OPTIONS p...

Page 5: ...ay Day of sending report to the server parameter ignored if Schedule Type 1 Registration Report Hours Decimal value of additional report hours binary vector extended info in user manual Report Delay D...

Page 6: ...con the blinking data sending icon will appear In the end the device will proceed to normal work showing periodically date hour and registered parameters value All of mentioned icons should flash cons...

Page 7: ...Description 0 not installed P pressure sensor X measurement range i e 0 1G 0 10 kPa 6G 0 600kPa 6A 80 600kPa abs DI DO 0 1 lub 2 digital inputs or outputs amount 2G modem 2G 3G modem 3G Sample markin...

Reviews: