39
13.1
H1 circuit service settings
Direct circuit (nonadjustable)
Name
Range**
Setting**
Description
Support
ON (radiators),OFF
ON
(radiators)
ON (Radiators)
– enables operation of the circuit,
OFF
– disables operation of the circuit,
Adjustment method
Fixed value, weather
weather
fixed value
– constant preset temperature of water in
nonadjustable circuit is maintained
weather
– water preset temperature of water in the circuit is set
with consideration to external temperature sensor readings.
Parameter is invisible if no external temperature sensor is
connected.
Weather control
Heating curve
0,1 … 4,0
1,2
The higher heating temperature, the higher temperature of water in
the heating circuit. Recommended settings:
floor heating:
0,2 -0,6
radiator heating:
1,0 - 1,6
Parameter becomes available when
Adjustment method
=
weather
.
heating curve shift
-
20 … 20
°C
Parameter enables to readjust the heating curve.
Parameter becomes available when
Adjustment method
=
weather
.
Constant water preset
temperature
20
… 85
45
°C
When
Adjustment method =
fixed value, heat source is disabled
when
constant water preset temperature
is reached. Source is
enabled again after the temperature drops by
heat source
hysteresis
value. Parameter is not available if
Adjustment method =
weather
.
Decreasing constant
water temperature
0…80
10°C
When
Regulation method
= constant value, then a constant set
temperature of water in the circuit is decreased for regulation
modes: NIGHT, AUTO, OUTSIDE HOME, HOLIDAY.
Room thermostat
selection
No
Panel 1
T1
…T3
Panel 1
Parameter assigns a room thermostat to the heating circuit.
No
– room temperature has no effect on the heating circuit,
Panel 1
– room temperature readings are received from the control
panel and they have an effect on a preset temperature of water in
th
e heating circuit. Name “Panel 1” can be changed in the main
menu to, e.g. “Living room” in case the panel is assembled in a
living room.
T1
… T3
– the controller receives ON/OFF signal from the universal
room thermostat. Caution: after using the universal room thermostat
connected to controller terminals, there is no further possibility of
correcting temperature of water in the circuit from the room
temperature! Therefore it is recommended to use the control panel
as a room thermostat.
Room thermostat function
Reduction,
Correction,
The
correction
Correction
Reduction
– exceeding a room preset temperature causes a
decrease of preset temperature of water in the heating circuit by
Water temperature reduction from thermostat
value.
Correction
– exceeding a room preset temperature causes a
temperature correction of water in the heating circuit. Correction is
proportional to a
temperature correction
value and to a difference
between preset and measured room temperature.
Thermostat + correction
– exceeding a room preset temperature
causes a temperature correction of water in the heating circuit and
decrease of preset temperature of water in the heating circuit by
Water temperature reduction from thermostat
value.
The correction
is proportional to the parameter value
room temperature correction
and proportional to the temperature difference between the set
temperature and the measured room temperature.
Room temperature
correction
0
…100
20
The higher parameter value the higher correction of set temperature
in the heat circuit.
Set water temperature in the heat circuit will be corrected by delT
value:
delT = (TsetR
– TmR)*
temperature correction
/ 10,
where:
TsetR - set room temperature,
TmR - measured room temperature.
Set temperature of water in the heat circuit will not be corrected in
Summary of Contents for ecoMAX920P2-I
Page 2: ......
Page 6: ...6...
Page 7: ...CONTROLLER OPERATION MANUAL ecoMAX920P2 I FOR THE USER...
Page 18: ......
Page 19: ...CONTROLLER ASSEMBLY AND SERVICE SETTINGS MANUAL ecoMAX920P2 I FOR THE INSTALLER...
Page 47: ...47...
Page 48: ...ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www plum pl...