INTRODUCTION

The Plasma Air PA600 is a needlepoint brush type ionizer producing an 
equal amount of positive and negative ions. This ionization equipment is 
effective in reducing harmful pollutants and odors by introducing positive 
and negative ions into the system airflow. This unit is highly versatile as it 
may be installed in an air handling unit, fan coil unit, PTAC, heat pump and 
even a ductless split system. The PA600 is self contained in a potted 
enclosure which has molded flanges with mounting holes. Models are 
available to accept 12V DC, 24V AC, 120V AC and 208 - 240V AC without 
the use of an external power supply.  

MECHANICAL INSTALLATION INSTRUCTIONS

GENERAL MOUNTING CRITERIA: 
1.

 Do not connect to power before mechanical installation is complete.

2.

 Mount ionization unit to allow access for general maintenance.

3.

 Mount the unit at or near the fan inlet using the holes in the mounting 

flanges, ensuring that the air stream flows over the 2 brushes 
simultaneously. See figures 1 & 2.

4.

 The unit should be mounted downstream of the filter.

5.

 For best results avoid locations directly after a cooling coil or humidifier.

LED INDICATOR LIGHT

POWER WIRES

IONIZATION BRUSHES

MOUNTING FLANGE

MOUNTING HOLE

A

IR

 F

LO

W

FIGURE 1

FAN

DISCHARGE

FAN INLET

IN LINE 500 mA

GLASS CARTRIDGE FUSE

CONNECT

TO POWER

FIGURE 2

PA600

MOUNTING HOLES