The 2 DIP switch settings and descriptions:
1 2
DIP
ON
1 2 3 4 5 6
DIP
ON
OFF
1
LFPP
Enable
Disable (default)
2
PoE
Legacy
BT (default)
LFPP means Link Fault Passthrough PoE Control.
LFPP ON:
1. The IGUP-805AT will disable PoE port once it detects the fiber
optic link is down.
2. The IGUP-805AT will turn on fiber alarm.
LFPP OFF: The IGUP-805AT LFPP is inactivated.(default)
2.4 Wiring the Power Inputs
The 6-contact terminal block connector on the top panel of Industrial PoE++
Media Converter is used for two 12-54V DC redundant power inputs. Please
follow the steps below to insert the power wire.
Caution
When performing any of the procedures like inserting the wires
or tightening the wire-clamp screws, make sure the power is
OFF to prevent from getting an electric shock.
1. Insert positive and negative DC power wires into contacts 1 and 2 for
POWER 1, or 5 and 6 for Power 2.
Max. Fault Alarm Loading: 24V, 1A
V1+
V2+
PWR1
PWR2
Alarm
DC Input:
12-54V , 6A max.
DIP
LFPP
PoE
1
2
ON
Enable
Legacy
OFF
Disable
BT
1 2
DIP
ON
1 2 3 4 5 6