20
Appendix B: Recommended Settings for Different Batteries
We suggest Nickel-cadmium battery and Lead-acid battery for BSP-360. You could
set the Battery type at Battery Management on the web.
Description
Specifications
Battery type
Nickel-cadmium Battery
System voltage
24V
Maximum input voltage
45V DC
Output voltage for load
Equal to battery’s voltage
Float charge voltage
27.2V DC (26.0~30.0V)
Absorption charge voltage
29.2V DC (28.0~32.0V)
LVD (Low Voltage
Disconnection)
22.2V DC (21.0~25.0V)
LVR (Low Voltage
Reconnection)
24.8V DC (23.0~27.0V)
Temperature compensation
Baseline@25°C
±40 mV/°C for NiCad type batteries, Charge
cut-off @ 55°C
Battery type
Lead-acid Battery (Default Setting)
System voltage
24V
Maximum input voltage
45V DC
Output voltage for load
Equal to battery’s voltage
Float charge voltage
27.2V DC (26.0~30.0V)
Absorption charge voltage
29.2V DC (28.0~32.0V)
LVD (Low Voltage
Disconnection)
22.2V DC (21.0~25.0V)
LVR (Low Voltage
Reconnection)
24.8V DC (23.0~27.0V)
Temperature compensation
Baseline@25°C
±60 mV/°C for lead acid type batteries, Charge
cut-off @ 55°C