1
Process Connection
DST100
5x60
6x15
6x50
6x100
Diameter x Lenght
A304 (AISI 304 - 899°C)
A316 (AISI 316 - 899°C)
Material type
0000
(no connector)
1/2”/ (sliding)
1/4”/ (sliding)
1/2”/F
(F = fixed)
1/4”/F
(F = fixed)
1/8”/F
(F = fixed)
1/2”/FNPT (F = fixed)
1/4”/FNPT (F = fixed)
DN25FO
(DN25 food)
DN25CL
(DN25 clamp)
Other..
Connector / Coupling
4 SP1 (Out1)
5 SP2 (Out2)
3 Us-
1 Us+
2 Out analogue
P
U
Pin Configuration P1
2
3
5
4
1
2
Main features
Box
93 x 37 mm
Power supply
15..30 VDC
Power consumption
Max 0,8 W
Operating conditions
Temperature -25..+85 °C, humidity 35..95 RH% (Cable PVC 22: -5°C ... +60°C)
Material
Sensor housing steel galvanised, display housing plastic
Weight
Approx. 189 g
Sealing
IP65 - FPM, NBR, EPDM
19
t_EP
Temperature end point
Temperature numeric value expressed with the selected measure unit for the retransmission on the analogue output.
Default:
value greater than f.s.
Range: 50% - 100% of the nominal temperature range expressed with the selected measure unit.
20
O_nP
Output zero point
Numeric starting value expressed in tension or current selected on parameter
Oana
.
NB: Value displayed but not editable.
Example: for
Oana
=
i
,
O_nP
= 4.00mA
Example 2: for
Oana
=
u
,
O_nP
= 0.00V
21
O_EP
Output end point
Numeric end value expressed in tension or current selected on parameter
Oana
.
NB: Value displayed but not editable.
Example: for
Oana
=
i
,
O_nP
= 20.00mA
Example 2: for
Oana
=
u
,
O_nP
= 10.00V
22
dAa
Damping for analogue output
Low-pass filter for analogue output. Time in seconds for the output stabilisation from 10% to 90% of the variation.
Example: temperature sensor 0..10 Bar,
dAa
= 1.00s: at instantaneous temperature switch from 0 to 10Bar, the output will take
approx. 1.2s. to stabilise from 4.00 to 20.00mA or from 0.00 to 10.00V
Range: 0.00..3.00.
Default
: 0.00
23
diSr
Display rotate
Display orientation / rotation 0° (normal) or 180°
yes
no
Default
24
diS
Display mode
Display mode defines the displayed value.
Ac-3
act
without the 3 less significant decimals**
Ac-2
act
without the 2 less significant decimals**
Ac-1
act
without the less significant decimal**
off
Switches off display after 5 sec.
hiGh
Maximum temperature value
Low
Minimum temperature value
Act
Actual temperature value.
Default
** .. Among those displayed.
25
Dupd
Display update rate
Display update rate, updates per second.
20
Every 20 seconds
5
Every 5 seconds
2
Every 2 seconds.
Default
1
Every 1 second
26
dia
Diagnostic mode
To activate a diagnostic mode.
on
the sensor simulates a temperature ramp in loop, from the min. to the max. value of the temperature range, in a cycle
time of approx. 5s. It is used to verify the functioning of the switching points and the analogue output.
off
Default
27
s.tim
Sample time
(logger)
A device integrated data logger
Range: steps of 0.0s up to 999.9s.
0.0 logger disabled.
Default
The logger stores values into a circular memory of 3500 points , with time selected in
s.tim
, instantaneous temperature value
and the status of SP1 and SP2 at sample time. At restart de old logger is deleted and a new one is overwritten. It is possible to
analyze the log through a software with NFC interface both with ON or OFF device.
28
code
Access code definition
0000
= no password.
Default
Password input digit by digit
To modify the password press
SET
and using
o
or
p
select the value of each digit. Press
SET
to modify the next digit. To end
the operation, press
SET
and confirm or not with
Yes
or
FaLs
.
NB: If par.
Code
is modified with a number different from
0000
, a new password is enabled and will be requested once (until the
next restard) to modify parameters and switching points.
DST100
Temperature transmitter
with display
User manual
PIXSYS s.r.l.
www.pixsys.net
[email protected] - [email protected]
online assistance: http://forum.pixsys.net
2300.10.283-RevA
Software Rev. 5.04
300718
Read carefully the safety guidelines and programming instructions
contained in this manual before using/connecting the device.