User manual - DRR460 -
21
3
Lo.L.i.
Lower Linear Input
(Word modbus 2003)
Range AN1 lower limit only for linear input. Ex: with input 4..20 mA this
parameter takes value associated to 4 mA.
-32767..+32767
,
Default
: 0.
4
up.L.i.
Upper Linear Input
(Word modbus 2004)
Range AN1 upper limit only for linear input. Ex: with input 4..20 mA this
parameter takes value associated to 20 mA.
-32767..+32767
.
Default
:10000
5
Pot.v.
Potentiometer Value
(Word modbus 2005)
Select potentiometer value
1..150 kohm
.
Default
: 10kohm
6
L.i.o.L.
Linear Input over Limits
(Word modbus 2006)
If linear input, allows process to go over limits (Par. 3 and 4).
0
Disabled (
Default
)
1 Enabled
7
o.cAL.
Offset Calibration
(Word modbus 2007)
Value added / subtracted to the process visualization (usually correcting the value of
environmental temperature).
-10000..+10000 [digit
1
] (degrees.tenths for temperature sensors).
Default
0.
8
G.caL.
Gain Calibration
(Word modbus 2008)
Percentage value that is multiplied for the process value (allows to calibrated the working point).
Ex: to correct the range from 0..1000°C showing 0..1010°C, set the par. to -1.0.
-1000 (100.0%)...+1000 (+100.0%),
Default
: 0.0.
9
Ltch
Latch-On
(Word modbus 2009)
Automatic setting of limits for linear inputs and potentiometers.
0
Disabled (
Default
)
1 Standard
2
Virtual zero
3
Linear virtual zero
10
FLtr.
Filter
(Word modbus 2010)
Analogue input reading filter: increases process stability on word 1000, 1100, 1200, 1232.
1...50. (
Default
: 1)
11÷15
Reserved Parameters - Group A
Reserved parameters - Group A