10 - DRR244 - 

User manual

5.1 

Wiring diagram

DRR244-13ABC-T

24 23 22

24...230V

AC/DC

B (+)

RS485

CT

PT100

TC

NI100 A\V

PTC NTC

A (-) DO2

(PNP)

DI2

(PNP)

DI1

(PNP)

+V

21 20 19

1

NO C

Q1

Q2

Q3

NC NO

NO 0V (PNP)

DO1 AO1

V/mA

C

C

NC

2

3

4

5

6

7

8

9 10 11 12

18 17 16 15 14 13

5.1.a 

Power Supply

SUPPLY

24...230

VAC/DC

24

23

Switching power supply 24..230 VAC/VDC ±15% 50/60 Hz - 9 Watt/VA.

Galvanic insulation (2500V).

5.1.b 

Analogue Input AI1

AI1

TC

Shield/Schermo

13

14

For thermocouples K, S, R, J, T, E, N, B.

•  Comply with polarity

•  For possible extensions, use compensated cable and terminals suitable for 

the thermocouples used (compensated).

•  When shielded cable is used, it should be grounded at one side only.

AI1

PT/NI100

Shield/Schermo

Rosso

Red

Bianco
White

Rosso

Red

13

14

15

For thermoresistances PT100, Ni100.

•  For the three-wire connection use wires with the same section.

•  For the two-wire connection short-circuit terminals 13 and 15

•  When shielded cable is used, it should be grounded at one side only.

RED/ROSSO

RED/ROSSO

WHITE/BIANCO

AI1

Shield/Schermo

PT

C/NT

C

15

14

For thermoresistances NTC, PTC, PT500, PT1000 and linear potentiome-

ters.

When shielded cable is used, it should be grounded at one side only to avoid 

ground loop currents.

AI1 V

mA

+V

Shield/Schermo

16

14

13

For linear signals in Volt and mA

•  Comply with polarity

•  When shielded cable is used, it should be grounded at one side only to 

avoid ground loop currents.

•  It’s possible to V at 12Vdc or 24Vdc, by configuring parameter 282 

V.out

 (GROUP R - 

diSP.

 - Display and interface).

Summary of Contents for DRR244

Page 1: ...DRR244 Controller Regolatore r gulateur User manual Manuale d uso Manuel utilisateur...

Page 2: ...conceived for applications related to nuclear power plants weapon systems flight control mass transportation systems Only qualified personnel should be allowed to use device and or service it and only...

Page 3: ...shielded cables and using separate conduits or ducts is recommended Attach a surge suppressor or noise filter to peripheral devices that generate noise in particular motors transformers solenoids mag...

Page 4: ...0 60 mV Pot Input 1 150 K CT 50 mA Tolerance 25 C 0 2 1 digit on F s for thermocou ple thermoresistance and V mA Cold junction accuracy 0 1 C C Impedence 0 10 V Ri 110 K 0 20 mA Ri 5 0 40 mV Ri 1 M R...

Page 5: ...3 DRR244 FNC SET C1 C2 A1 A2 A3 TUN MAN REM 5 Electrical wirings This controller has been designed and manufactured in conformity to Low Voltage Directive 2006 95 EC 2014 35 EU LVD and EMC Directive 2...

Page 6: ...at one side only AI1 PT NI100 Shield Schermo Rosso Red Bianco White Rosso Red 13 14 15 For thermoresistances PT100 Ni100 For the three wire connection use wires with the same section For the two wire...

Page 7: ...ons 5 1 f Digital output 0V DO1 PNP DO2 PNP 9 10 19 Digital output PNP including SSR for command or alarm Range 12 VDC 25 mA or 24 VDC 15mA selectable by parameter 282 v out 5 1 g Analogue output AO1...

Page 8: ...ameter value being inserted 6 1 Meaning of Status Lights Led 3 C1 ON when the command output 1 is active In versions with single analog input it is ON when the valve is opening In the versions with tw...

Reviews: