20
- ATR227 -
User manual
30
a.1.Ld.
Alarm 1 Led (Password 5678)
Defines the state of
A1
led corresponding to the relative contact
o.c.
ON with open contact
c.c.
ON with closed contact (
Default
)
31
a.1.s.e.
Alarm 1 State Error (Password 5678)
State of contact for alarm 1 output in case of error
o.c.
Open contact (
Default
)
c.c.
Closed contact
32
a.1.sp.
Alarm 1 Setpoint Protection (Password 1234)
Does not allow the user to modify setpoint
free
Modifiable by the user (
Default
)
Lock
Locked
Hide
Locked and hidden
33
a1.re.
Alarm 1 Reset (Password 5678)
Type of Reset for contact of alarm 1
are.
Automatic Reset (
Default
)
mre.
Manual reset (by keyboard)
SET
mre.s.
Manual Reset Stored (keeps relay status also after an eventual power
failure)
34
a.1.de.
Alarm 1 Delay (Password 5678)
-900..+900 secondi.
Default
: 0.
Negative: delay in alarm output phase
Positive: delay in alarm entry phase.
35
AL.2
Alarm 2 (Password 1234)
Alarm 2 selection.
dis.
Disabled (
Default
)
A. AL.
Absolute / threshold, referring to process
b. AL.
Band alarm
H.d.AL.
Upper deviation alarm
L.d.AL.
Lower deviation alarm