28 - ATR224 - DRR224 - User manual
GROUP M -
d.i. 1
- Digital input 1
231
d.i.1.f.
Digital Input 1 Function
Digital input 1 functioning.
diSab.
Disabled (
Default
)
2t. sw.
2 Setpoints Switch
rUn
Run
tune
Performing manual tune
au.ma.i.
Automatic / Manual Impulse (if enabled on parameter 48 or 67)
au.ma.c.
Automatic / Manual Contact (if enabled on parameter 48 or 67)
act.tY.
Action Type. Cooling regulat. if D.I. is active, otherwise heating reg.
M. reS.
Manual reset. Reset the outputs if selected as manual reset.
232
d.i.1.c.
Digital Input 1 Contact
Defines the resting contact of the digital input 1.
n.open
Normally open (
Default
)
n.cLos.
Normally closed
235÷238
Reserved Parameters - Group M
Reserved parameters - Group M
GROUP Q -
sft.s
- Soft-start and mini cycle
264
SS.TY.
Soft-Start Type
Enables and selects the soft-start type
diSab.
Disabled (
Default
)
Grad.
Gradient
Perc.
Percentage (only with pre-programmed cycle disabled)
266
SS.Gr.
Soft-Start Gradient
Rising/falling gradient for soft-start and pre-programmed cycle.
0..20000 Digit/hour
(degrees.tenths/hour if temperature). (
Default
: 100.0)
267
SS.Pe.
Soft-Start Percentage
Output percentage during soft-start function.
0..100%. (
Default
: 50%)
268
SS.tH.
Soft-Start Threshold
Threshold under which the soft-start percentage function is activated, at starting.
-9999...30000 [digit
] (degrees.tenths for temp. sensors) (
Default
: 1000)
269
SS.ti.
Soft-Start Time
Max. Softstart duration: if the processs will not reach the threshold selected on par. SS.tH. within
the selected time, the controller starts to regulate on setpoint.
00:00
Disabled
00:01-24:00
hh:mm (
Default
: 00:15)