Pittway Notifier ACM-8R Manual Download Page 2

WARNING 

Several different sources of power can be

connected to the fire alarm control panel.

  Disconnect all

sources of power before servicing.  Control unit and

associated equipment may be damaged by removing and/

or inserting cards, modules, or interconnecting cables while

the unit is energized.  Do not attempt to install, service,

or operate this unit until this manual is read and understood.

CAUTION - 

System Reacceptance Test after Software

Changes:

 To ensure proper system operation, this product

must be tested in accordance with NFPA 72-1993 Chapter

7 after any programming operation or change in site-

specific software.   Reacceptance testing is required after

any change, addition or deletion of system components,

or after any modification, repair or adjustment to system

hardware or wiring.

All components, circuits, system operations, or software

functions known to be affected by a change must be 100%

tested.  In addition, to ensure that other operations are not

inadvertently affected, at least 10% of initiating devices

that are not directly affected by the change, up to a

maximum of 50 devices, must be tested and proper

system operation verified.

This system  

meets NFPA requirements for

operation at 0-49

O

 C/32-120

O

  F

 

 and at a relative

humidity of 85% RH (non-condensing) at 30

C/86

O

F.  However, the useful life of the system's standby

batteries and the electronic components may be

adversely affected by extreme temperature ranges

and humidity.  Therefore, it is recommended that this

system and its peripherals be installed in an

environment with a nominal room temperature of 15-

27

O

 C/60-80

O

 F.

Verify that wire sizes are adequate

 for all initiating and

indicating device loops.  Most devices cannot tolerate

more than a 10% I.R. drop from the specified device

voltage.

Like all solid state electronic devices,

 this system may

operate erratically or can be damaged when subjected to

lightning induced transients.  Although no system is completely

immune from lightning transients and interferences, proper

grounding will reduce susceptibility.  

Overhead or outside

aerial wiring is not recommended, due to an increased suscep-

tibility to nearby lightning strikes.  

Consult with the Technical

Services Department if any problems are anticipated or en-

countered.

Disconnect AC power and batteries

 prior to removing or

inserting circuit boards.  Failure to do so can damage circuits.

Remove all electronic assemblies

 prior to any drilling, filing,

reaming, or punching of the enclosure.  When possible, make

all cable entries from the sides or rear.  Before making

modifications, verify that they will not interfere with battery,

transformer, and printed circuit board location.

Do not tighten screw terminals

 more than 9 in-lbs.  Over

tightening may damage threads, resulting in reduced terminal

contact pressure and difficulty with screw terminal removal.

This system 

contains static-sensitive components.  Always

ground yourself with a proper wrist strap before handling any

circuits so that static charges are removed from the body.  Use

static suppressive packaging to protect electronic assemblies

removed from the unit.

Follow the instructions

 in the installation, operating, and pro-

gramming manuals.  These instructions must be followed to avoid

damage to the control panel and associated equipment.  FACP

operation and reliability depend upon proper installation.

Audible warning devices

 such as bells may not alert people

if these devices are located on the other side of closed or

partly open doors or are located on another floor of a building.

A fire alarm system

 will not operate without any electrical

power.  If AC power fails, the system will operate from

standby batteries only for a specified time.

Rate-of-Rise heat detectors

 may be subject to reduced

sensitivity over time.  For this reason, the rate-of-rise feature

of each detector should be tested at least once per year by

a qualified fire protection specialist.

Equipment used in the system

 may not be technically

compatible with the control.  It is essential to use only

equipment listed for service with your control panel.

Telephone lines

 needed to transmit alarm signals from a

premise to a central monitoring station may be out of service

or temporarily disabled.

The most common cause

 of fire alarm malfunctions, how-

ever, is inadequate maintenance.  All devices and system

wiring should be tested and maintained by professional fire

alarm installers following written procedures supplied with

each device.  System inspection and testing should be sched-

uled monthly or as required by National and/or local fire codes.

Adequate written records of all inspections should be kept.

An automatic fire alarm system

 - typically made up of smoke

detectors, heat detectors, manual pull stations, audible warn-

ing devices, and a fire alarm control with remote notification

capability can provide early warning of a developing fire.  Such

a system, however, does not assure protection against prop-

erty damage or loss of life resulting from a fire.

Any fire alarm system

 may fail for a variety of reasons:

Smoke detectors

 may not sense fire where smoke cannot

reach the detectors such as in chimneys, in walls, or roofs, or

on the other side of closed doors.  Smoke detectors also may

not sense a fire on another level or floor of a building.  A

second floor detector, for example, may not sense a first floor

or basement fire.  Furthermore, all types of smoke detectors

- both ionization and photoelectric types, have sensing limi-

tations.  No type of smoke detector can sense every kind of

fire caused by carelessness and safety hazards like smoking

in bed, violent explosions, escaping gas, improper storage of

flammable materials, overloaded electrical circuits, children

playing with matches, or arson.

IMPORTANT! 

 Smoke detectors 

must be installed in the

same room as the control panel and in rooms used by the

system for the connection of alarm transmission wiring,

communications, signaling, and/or power.

  If detectors are

not so located, a developing fire may damage the alarm

system, crippling its ability to report a fire.

While installing a fire alarm system may make lower insur-

ance rates possible, it is not a substitute for fire insurance!

Fire Alarm System Limitations

Installation Precautions

Adherence to the following will aid in problem-free

installation with long-term reliability:

Technical Publishing

          Document PRECAUSM.PM6  07/12/96

www.PDF-Zoo.com

firealarmresources.com

Summary of Contents for Notifier ACM-8R

Page 1: ...97 Revision 07 24 97 Revision 07 24 97 Revision D1 For the System 500 System 5000 AFP 200 AM2020 AFP1010 and SFP 1024 Fire Alarm Control Panels The ACM 8R Annunciator Control Module P N 15342 D1 ECN...

Page 2: ...unit Follow the instructions in the installation operating and pro grammingmanuals Theseinstructionsmustbefollowedtoavoid damage to the control panel and associated equipment FACP operation and relia...

Page 3: ...nciators 12 Figure 3 4 ACM 8R Relay Terminal Assignments 13 Table 3 1 Relay Assignments 14 Mapping the ACM 8R relays 14 Row and Module Arrangement 15 Relay Assignment Examples 15 Figure 3 5 Connecting...

Page 4: ...rcuit including AFM Series annunciators LDM Series annunciators LED 10N annunciators and UDACTs Universal Digital Alarm Communicator Transmitter EIA 485 bus compatible accessories are designed to prov...

Page 5: ...Note for AM2020 installations only SIB 2048 can support two EIA 485 circuits each capable of spanning 6 000 feet 16 AWG For more details refer to Appendix B ACS and the AM2020 Wiring Specifications T...

Page 6: ...configured for Receive Only operation they cannot send information to the system such as Module Trouble indications Wiring to Receive Only annunciators may be supervised by installing the modules ups...

Page 7: ...on between the negative battery terminals of each supply must be made Fire Alarm Control Panel Power Loop EIA 485 Circuit EIA 485 Circuit Annunciator in a Backbox powered from Control Panel A common t...

Page 8: ...M 8R draws its power from the control panel and must be considered when calculating the primary and secondary power supply requirements for the system Each annunciator module must be accounted for in...

Page 9: ...ive screws on the top of the relay module and the two mounting holes on the bottom of the relay module with the pem standoffs on the backbox Secure with captive screws at top and with two loose screws...

Page 10: ...ve 25 VRMS motor control circuits or SCR power circuits All enclosures including the FACP backbox must be connected to earth ground Never use the shield for grounding purposes Terminate the EIA 485 sh...

Page 11: ...2 Set ON if the ACM 8R is to function in Receive Only mode on the EIA 485 circuit ALM RCV ONLY ONLY MODE SELECT SW4 TENS ONES SW1 SW2 ADDRESS SELECT SW3 Relay Assignment DIP Switches refer to Table 3...

Page 12: ...ting screw on the backbox or cabinet Connect 24 VDC Power to the annunciator This power must be power limited but need not be supervised by a power supervision relay since it is inherently supervised...

Page 13: ...map these relays will be assigned refer to Table 3 1 For information on wiring limitations refer to the UL Power limited Wiring Requirements section Figure 3 4 ACM 8R Relay Terminal Assignments Normal...

Page 14: ...7 40 41 44 45 48 49 52 52 56 57 60 61 64 Table 3 1 Relay Assignments per EIA 485 address Mapping Note Note that Table 3 1 outlines relay assignments at a given EIA 485 address A single EIA 485 address...

Page 15: ...le arrangement Note This correlation exists for each EIA 485 address That is the third cabinet row would become the 1st cabinet row at address 02 SW3 Cabinet Row select one only Set ON for 1st row Set...

Page 16: ...ny module in the Sys tem 5000 To assign the ACM 8R to a mod ule two switches on SW3 must be set to ON Example To as signtheACM 8Rtothe thirdmoduleinthesec ond row of a System 5000 set switches 3 and 6...

Page 17: ...modulehalfintheSys tem 5000 To assign the ACM 8R to a mod ule half two switches on SW3 must be set to ON The two switches that must be set ON are indicated below themodulehalf Example To assign theACM...

Page 18: ...ght hand L series board set switches 3 and 6 on SW3 to ON set the other six switches to OFF 2 6 3 6 Address 01 Relay Assignment Example System 500 Alarm Trouble Mode The ACM 8R can follow the alarm an...

Page 19: ...assis EIA 485 Loop 1 EIA 485 Loop 1 EIA 485 Loop 2 EIA 485 Loop 2 EIA 485 to ACM 8R TB2 3 EIA 485 to ACM 8R TB2 2 CPU 500 EIA 485 to ACM 8R TB2 3 EIA 485 to ACM 8R TB2 2 CPU 5000 EIA 485 Connection Th...

Page 20: ...do not cut jumper JP5 The total amount of current drawn from these terminals cannot exceed that rating in standby or in alarm 24 VDC Power to ACM 8R TB1 2 Common to ACM 8R TB1 4 MPS 24B Main Power Su...

Page 21: ...d circuits Different applications may require different conduit knockouts to be used Any conduit knockouts may be used provided that the nonpower limited wiring remain separated from the power limited...

Page 22: ...e CPU Points Activated Notification Circuits 1 and 2 the Remote Signaling Municipal Tie circuit and the Alarm Relay Activation shown when System 5000 has been programmed to display Output Status Softw...

Page 23: ...t of the CPU 5000 Note that an annunciator cannot be used to execute manual ON OFF control of intelligent AIM 200 points The option provides annunciation of up to 256 points for the System 5000 broken...

Page 24: ...tions Software Zones 1 240 XP Series Transponder System Power and Audio Supply Supervision XPP 1 Form C Alarm and Trouble Relays XPC Control XPM Monitor and XPR Relay Module Circuits Software Required...

Page 25: ...st be programmed from the AM2020 AFP1010 before the ACM 8R will function The AM2020 AFP1010 employ the following format for annunciator points A xx P yy Annunciator address Annunciator points in the r...

Page 26: ...Points Activated Notification Circuits 1 and 2 the Remote Signaling Munici pal Tie circuit and the Alarm Relay Trouble Indication Communication between the CPU and the ACM 8R is accomplished over a t...

Page 27: ...s eight system points and software zones Z1 through Z56 are automatically mapped to annunciator address 01 points 1 through 64 A1P1 A1P64 Zones Z57 through Z99 are mapped to annunciator address 02 poi...

Page 28: ...Switches 3 On 5 On ACM 8R Dip Switches 4 On 5 On ACM 8R Dip Switches 1 On 6 On ACM 8R Dip Switches 2 On 6 On ACM 8R Dip Switches 3 On 6 On ACM 8R Dip Switches 4 On 6 On Annunciator Address 01 AFP 200...

Page 29: ...Dip Switches 4 On 5 On ACM 8R Dip Switches 1 On 6 On ACM 8R Dip Switches 2 On 6 On ACM 8R Dip Switches 3 On 6 On ACM 8R Dip Switches 4 On 6 On ACM 8R Dip Switches 1 On 7 On ACM 8R Dip Switches 2 On 7...

Page 30: ...e Up to 32 ACM 8R Relay Control Modules may be placed onto the EIA 485 communication bus if no other devices are installed on the bus CAUTION It is vitally important that following relay programming a...

Page 31: ...1 y a l e R 2 Z 2 y a l e R R 8 M C A d n 2 3 Z 3 y a l e R N O 2 3 W S 4 Z 4 y a l e R N O 5 3 W S 5 Z 5 y a l e R F F O s r e h t o l l A 6 Z 6 y a l e R 7 Z 7 y a l e R 8 Z 8 y a l e R 9 Z 1 y a l...

Page 32: ...W S 3 Z 3 y a l e R 7 y a l e R N O 5 3 W S 4 Z 4 y a l e R 8 y a l e R F F O s r e h t o l l A 5 Z 1 y a l e R 5 y a l e R R 8 M C A h t 4 6 Z 2 y a l e R 6 y a l e R N O 4 3 W S 7 Z 3 y a l e R 7 y...

Page 33: ...ACM 8R for Receive Only SW4 2 ON and the other for Receive Transmit SW4 2 OFF Set switch SW3 on one ACM 8R so that SW3 2 ON and SW3 5 ON and the remaining switches are OFF Set SW3 on the other ACM 8R...

Page 34: ...maining SW3 switches to OFF On the last ACM 8R set SW3 1 ON SW3 6 ON and the remaining SW3 switches to OFF Refer to the following charts 4 2 0 1 P F S e n o Z R 8 M C A m r a l A y a l e R R 8 M C A e...

Page 35: ...M 8R module contains eight relays two ACM 8R modules are required for 10 zones Set the Mode Select switch SW4 for alarm only on both ACM 8Rs SW4 1 ON Set the first ACM 8R on the bus for Receive Only S...

Page 36: ...se ACM 8Rs are set to address 03 Set the Mode Select switch SW4 for alarm only on both Alarm Only ACM 8Rs SW4 1 ON Set the first ACM 8R with address 03 for Receive Only SW4 2 ON and the second ACM 8R...

Page 37: ...set to Address 03 Alarm Only Receive Only Receive Transmit SW3 2 ON SW3 5 ON SW4 1 ON SW4 2 ON SW3 3 ON SW3 5 ON SW4 1 ON SW4 2 OFF SW3 3 ON SW3 5 ON SW4 1 OFF SW4 2 ON SW3 4 ON SW3 5 ON SW4 1 OFF SW4...

Page 38: ...38 38 38 38 38 Document 15342 Rev D1 07 24 97 P N 15342 D1 Notes www PDF Zoo com firealarmresources com...

Page 39: ...39 39 39 39 39 Document 15342 Rev D1 07 24 97 P N 15342 D1 www PDF Zoo com firealarmresources com...

Page 40: ...only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the...

Reviews: