8. WIRING DIAGRAM
8.3 Common wiring
Recommended wire size
●
Use cooper power supply wires.
●
Follow local codes and regulations when select field wires, and all the above are the minimum
wire size.
●
When transmitting cable length is longer than 262ft. (80m), a larger wire size should be selected.
●
Install main switch and ELB for each system separately. Select the high response type ELB that
acts within 0.1second.
Max
.
Running
Current
(
A
):
REFER
TO
NAMEPLATE
NOTE:
Model
(Capacity)
Power Supply
ELB
Power Source
Cable Size
Transmitting
Cable Size
Rated Current
(A)
Nominal Sensitive
Current (mA)
24K
208/230V ~/60Hz
25
30
3×12AWG
4×16AWG
36K
208/230V ~/60Hz
35
30
3×10AWG
4×16AWG
60K
208/230V ~/60Hz
60
30
3×8AWG
4×16AWG
33